41RML100 – Combined smoke / heat detector with isolator
17/06/2020 14:06
41RML100
Address
Loop Number
Device Zone
11
2
1
Enabled
Normal
Device State
More
Remove
OFF
Name
17/06/2020 14:06
Check
Smoke [%] / Temperature [°C]
ON
Led Blink
Device Group
Low
Day Alarm Level
Night Alarm Level
1.0
Software Revision
2868099610
ID
No RI Out
0
Low
T (ENABLED)
T (ENABLED)
The figure shows the settings screen for addressed detector 41RML100.
Press “MORE” to access additional settings:
•
Smoke [%] / Temperature [°C]
: press “Check” to access the parameter viewing screen:
◊
Smoke
: shows the percentage of the current level of smoke in the optical chamber of the detector.
◊
Sensor contamination level
: shows the percentage of the current level of contamination in the optical chamber of the
detector.
◊
Alarm threshold (°C)
: view the detector activation temperature, in degrees Centigrade.
◊
Temperature (°C)
: view the current temperature of the room, in degrees Centigrade.
•
LED Blink
: select ON/OFF to enable/disable LED indications for the device.
•
Device Group
: setting for linking a detector to a detector group. Enter a group number (>0) in the editable field; the
detector in question will be assigned to that specific group. This enables the button allowing that detector to activate any
remote light Art. 48FPT100 connected to any detector belonging to the SAME group.
•
Day Alarm level*
: sets the degree of sensitivity for the optical part of the detector in Day Mode. Press the dedicated button
to enable / disable the thermal part.
◊
Sensitivity Level
: there are 4 levels for setting the alarm sensitivity level: High, Normal, Middle and Low. To change the
sensitivity level, press the active button next to the field and choose a new level from the list.
◊
Thermal part
: for this device only, the installer can enable or disable the thermal part of the detector, by pressing the
dedicated button (T/ENABLED – T/DISABLED).
The temperature class of the 41RML100 detector is set as
A1R (58º, RoR)
and cannot be changed.
•
Night Alarm level*
: sets the degree of sensitivity for the optical part of the detector in Night Mode. Press the dedicated
button to enable / disable the thermal part.
The settings for the alarm level and thermal part are the same as listed above for the “Day Alarm Level”.
Caution: the optical part and the thermal part of the detector cannot both be disabled at the same time!
* Note
: in normal panel operating conditions, an asterisk appears next to the Alarm Level to identify the current operating mode
(day / night) of the fire panel (this can be changed via the maintenance menu).
To save any new parameters, press “Save” on the main device screen.
32