European Safety Systems Ltd.

  Impress House, Mansell Road, Acton, London W3 7QH 

 

 

 

 

 

[email protected]  Tel: +44 (0)208 743 8880 

Document D150-00-051-IS   Issue 7  26-08-20 

 

 

Sheet 1 of 3 

 

 

 

www.e2s.com  Fax +44 (0)208 740 4200 

 

 

BExCP3B-BG, BExCP3D-BG & 
BExCP3E-BG 
Manual  Call  Point 

–  Break  Glass 

With Resistor Modules 

For use in Flammable Gas and 
Combustible Dust Atmospheres. 

 

 

1) 

Introduction 

The BExCP3B-BG / BExCP3D-BG / BExCP3E-BG 
is a break glass manual call point which is certified 
to  the  European  and  International  Gas  and  Dust 
standards. The  unit  meets  the requirements  of the 
ATEX directive 2014/34/EU and IECEx scheme. 
 
The  call  point  can  be  used  in  hazardous  areas 
where  potentially  flammable  gas  and  dust 
atmospheres may be present.  

 

All units have up to two of the following series and/ 
or EOL devices: 

 

Monitoring resistors per module: - 

 

BExCP3B-BG - 2.0W Max 

 

BExCP3D-BG - 1.0W Max  

 

BExCP3E-BG - 1.75W Max  

 

Monitoring diode 

 

Monitoring Zener diode 

 
The  units are Group II, EPL (equipment  protection 
level) G

b. The equipment is certified ‘Ex db eb mb 

IIC  T4  Gb’  and  as  such  may  be  used  in  Zones  1 
and  2 with  flammable  gases and vapours with gas 

groups  IIA,  IIB  &  IIC  and  temperature  classes  T1, 
T2, T3 and T4. 
 
These  units  are  also  Group  III,  EPL  Db.  The 
equipment is certified 
‘Ex tb IIIC T60ºC Db’ (BExCP3B-BG), 
‘Ex tb IIIC T80ºC Db’ (BExCP3D-BG), 
‘Ex tb IIIC T75ºC Db’ (BExCP3E-BG) 
and  as

 

such  may  be  used  in  Zones  21  and  22  for 

combustible dusts groups IIIA, IIIB & IIIC. 

 
2) 

Ratings & Markings 

All  units  have  a  rating  label,  which  carries  the 
following important information: - 
 
Unit Type No.: 
BExCP3B-BG Manual Call Point 
BExCP3D-BG Manual Call Point 
BExCP3E-BG Manual Call Point 
 
Input Voltages 
48VDC nominal   56VDC Max   0.75A Max 
24VDC nominal   28VDC Max   5.0A Max Resistive 
Load; 3.0A Max Inductive Load 
12VDC nominal   15VDC Max   5.0A Max 
6VDC nominal     9VDC Max   5.0A Max 
 
Code: 
BExCP3B-BG 

      

Ex db eb mb IIC T4 Gb     
Ex tb IIIC T60ºC Db 

     

IP66 

 

     

–40ºC <= Ta <= +50ºC      
 
BExCP3D-BG 

    BExCP3E-BG 

Ex db eb mb IIC T4 Gb    Ex db eb mb IIC T4 Gb 
Ex tb IIIC T80ºC Db         Ex tb IIIC T75ºC Db 
IP66 

 

    IP66 

–40ºC <= Ta <= +70ºC    –40ºC <= Ta <= +65ºC 
 
Certificate No.: 
SIRA 09ATEX3286X 
IECEx SIR 09.0121X 
 
Epsilon x:                           II 2GD 
 
CE Marking 
Notified body No.               2813 
 
Year/Serial No. i.e. 20/1CP3BBG000001 

Or  

  20/1CP3DBG000001 

Or 

  20/1CP3EBG000001 

 
WARNING - DO NOT OPEN WHEN AN 
EXPLOSIVE ATMOSPHERE MAY BE PRESENT 

 
3) 

Type Approval Standards 

The  call  point  has  an  EC  Type  examination 
certificate issued by SIRA and have been approved 
to the following standards: - 
 
EN60079-0:2018 / IEC60079-0:2017 
EN60079-1:2014 / IEC60079-1:2014 
EN60079-7:2015 / IEC60079-7:2017 
EN60079-18:2015 / IEC60079-18:2014 
EN60079-31:2014 / IEC60079-31:2013 
 
The equipment is certified for use in ambient 
temperatures in the range  
BExCP3B-BG -40

o

C to +50

o

BExCP3D-BG -40

o

C to +70

o

C  

BExCP3E-BG -40

o

C to +65

o

C  

 
and shall not be used outside this range. 
 

4) 

Installation Requirements 

Installation  of  this  equipment  shall  only  be  carried 
out  by  suitably  trained  personnel  in  accordance 
with the applicable code of practice e.g.  
IEC 60079-14/EN 60079-14 

 

Repair of this equipment shall only be carried out 
by the manufacturer or in accordance with the 
applicable code of practice e.g. IEC 60079-19/EN 
60079-19. 
 
Refer  to  certificates  SIRA  09ATEX3286X  and 
IECEx SIR 09.0121X for special conditions of safe 
use. 
 
The  certification  of  this  equipment  relies  on  the 
following materials used in its construction: 
 
Enclosure:

 

Aluminium  Pressure  Die  Cast  Body 

LM6 
 
Through enclosure mechanism: Plastic Nylon Zytel 
Injection Moulded 
 
Sealing  of  enclosure  and  mechanism:  O-ring 
Acrylonitrile-Butadiene Rubber  
 
Potting Compound of resistors where  used: Epoxy 
Resin 
 
If the equipment is likely to  come into  contact with 
aggressive  substances,  then  it  is  the  responsibility 
of the user to take suitable precautions that prevent 
it from being adversely affected, thus ensuring that 
the type of protection is not compromised. 

 
“Aggressive  substances”  -  e.g.  acidic  liquids  or 
gases that may attack metals, or solvents that may 
affect polymeric materials. 
 
“Suitable precautions” - e.g. regular checks as part 
of  routine  inspections  or  establishing  from  the 
material’s  data  sheet  that  it  is  resistant  to  specific 
chemicals. 
 

5) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access  for  operation  and  testing.  The  unit  should 
be  mounted  using  the  4  off  fixing  holes  which  will 
accept up to M4 sized fixings. 
 

 

View of base unit showing fixing centers. 
 
To  gain  access  to  the  mounting  holes  in  the  base 
the front cover must be removed. This is achieved 
by removing the 4 off M4 cap head bolts holding on 
the cover.           

 

 

 

INSTRUCTION MANUAL 

BExCP3B-BG, BExCP3D-BG & BExCP3E-BG Break Glass Manual Call Point 

For use in Flammable Gas and Dust Atmospheres 

 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 
and if it does, it will only exist for a short time. 

  

 

Reviews: