DM2010 Manual Call Point Installation Sheet 

EN  IT 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EN: Installation Sheet 

Description  

The DM2010 manual call point is designed for use in Aritech 
analogue addressable fire alarm systems and include models 
for indoor and outdoor use. 

Installation 

Caution: 

This product must be installed by qualified personnel 

adhering to the CEN/TS 54-14 standard and any other 
applicable local authority laws. 

Electrical connections 

Connect to the DM2010 connection block (Figure 

2

) as follows: 

1.  Line in (positive) 
2.  Line out (positive) 
3.  Line in (negative) 
4.  Line out (negative) 

Addressing 

Use the DIP switch (Figure 1) to allocate a device address 
from 1 to 128 (see page 3). 

Maintenance 

Basic maintenance consists of a yearly inspection. Do not 
modify internal wiring or circuitry. 

Specifications 

 

Voltage 

17 to 28 VDC 

Current consumption 
 

Standby 

 

Alarm 

 

max. 250 ųA

 

max. 2.5 mA 

Cable size 
 

Minimum 

 

Maximum 

 
0.8 mm2 
2.5 mm2 

IP rating 
 

DM2010, DM2010-18 

 

DM2010E, DM2010E-18 

 
IP24D 
IP67 

Operating temperature 
 

DM2010, DM2010-18 

 

DM2010E, DM2010E-18 

 

10°C to +55°C 

25°C to +70°C 

Storage temperature 
 

DM2010, DM2010-18 

 

DM2010E, DM2010E-18 

 

10°C to +70°C 

25°C to +70°C 

Relative humidity 

10% to 95% noncondensing 

Dimensions (W × H × D) 
 

DM2010, DM2010-18 

 

DM2010E, DM2010E-18 

 
89 x 93 x 27.5 mm [1] 
97.5 x 93 x 27.5 mm [1] 

Weight 
 

DM2010, DM2010-18 

 

DM2010E, DM2010E-18 

 
180 g 
350 g 

[1] Excluding surface mount

 

Summary of Contents for DM2010

Page 1: ...Line in negative 4 Line out negative Addressing Use the DIP switch Figure 1 to allocate a device address from 1 to 128 see page 3 Maintenance Basic maintenance consists of a yearly inspection Do not modify internal wiring or circuitry Specifications Voltage 17 to 28 VDC Current consumption Standby Alarm max 250 ųA max 2 5 mA Cable size Minimum Maximum 0 8 mm2 2 5 mm2 IP rating DM2010 DM2010 18 DM2...

Page 2: ...ione incendio analogico indirizzati Aritech e includono modelli per uso interno ed esterno Installazione Attenzione Questo prodotto deve essere installato da personale qualificato in conformità alla norma CEN TS 54 14 e a tutte le leggi locali in vigore Collegamenti elettrici Collegare la morsettiera di connessione del DM2010 figura 2 come indicato di seguito 1 Ingresso linea positivo 2 Uscita lin...

Page 3: ...zione del prodotto Vedere il numero di modello sull etichetta di identificazione del prodotto I prodotti contrassegnati con questo simbolo non possono essere smaltiti nei comuni contenitori per lo smaltimento rifiuti nell Unione Europea Per il loro corretto smaltimento potete restituirli al vostro fornitore locale a seguito dell acquisto di un prodotto nuovo equivalente oppure rivolgervi e consegn...

Page 4: ... 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 ...

Reviews: