background image

 

 

European Safety Systems Ltd.

  Impress House, Mansell Road, Acton, London W3 7QH 

 

 

 

 

 

[email protected]  Tel: +44 (0)208 743 8880 

Document D150-00-051-IS   Issue 7  26-08-20 

 

 

Sheet 2 of 3 

 

 

 

www.e2s.com  Fax +44 (0)208 740 4200 

 

Once  the  screws  are  removed  the  cover  will  hang 
down  out  of  the  way  to  gain  access  to  the  Ex  e 
terminal  block,  the  internal  earth  terminal  and 
mounting hole recesses. 
 

6) 

Earthing 

The  unit  has  both  internal  and  external  earth 
terminals. 
It  is  recommended  that  a  cable  crimp  lug  is  used 
on the earth wires. 
The  internal  earth  wire  is  placed  under  a  earth 
clamp  which  will  stop  the  cable  twisting.  This  is 
secured by an M4 screw and spring washer. 
The  external  earth  lug  should  be  located  between 
the two  M5 washers provided and securely locked 
down with the M5 spring washer and two locknuts. 
 

 

Internal Earth 
terminal 

 

 

External 

 

 

               Earth Stud 

 

Ex e terminal block 

 
Note: Depending on options chosen an 8-Way DIN 
Rail or 6-Way terminal block may be selected. 
 

7) 

Cable connections 

There  are  3  off  cable  entry  holes  suitable  for 
M20x1.5  Ex  e  approved  cable  glands  or  stopping 
plugs 
 
The unit can be wired in a number of different ways 
depending  on  the  resistor  combination  selected. 
For detail, refer to wiring schematic D150-06-051. 
 
EOL (End of line) device;  
resistor 

– ExxxR / diode – ED1 / zener – ExxxZ  

Series (In line) device;  
resistor 

– SxxxR / diode – SD1 / zener – SxxxZ 

Microswitch 1 = M/S 1 
 

Voltage 
option 

Max 
Voltage 

Min resistor 
value 
allowable in 
module 
Type B unit 
(2.0W) 

Min resistor 
value 
allowable 
in module 
Type D unit 
(1.0W) 

Min resistor 
value 
allowable 
in module 
Type E unit 
(1.75W) 

6 V dc 

9 V dc 

47 ohms 

91 ohms 

51 ohms 

12V dc 

15 V dc 

120 ohms 

240 ohms 

150 ohms 

24V dc 

28 V dc 

470 ohms 

820 ohms 

510 ohms 

48V dc 

56 V dc 

1K8 ohms 

3K3 ohms 

2K0 ohms 

 
When  wiring  to  Increased  Safety  terminal 
enclosures, you are only  permitted to  connect one 
wire into  each way on the terminal block, unless  a 
pair of wires are crimped into a suitable ferrule. 
For the six-way terminal block wire sizes allowable 
are 0.5mm² to 4.0mm². For the 8-way DIN rail wire 
sizes allowable are 0.5mm² to 2.5mm². 
 
Leads connected to the terminals shall be insulated 
for the appropriate voltage and this insulation shall 
extend to within 1mm of the metal of the terminal  
throat.  They  shall  only  be  installed  and  wired  with 
cable in an ambient temperature of -10°C to +80°C 
 
All  terminal  screws,  used  or  unused,  shall  be 
tightened down to between 0.5 Nm and 0.7 Nm 
 

7.1) Fitted LED, Diode or Zener Diode 

If a  diode module is  pre-fitted as  either an EOL or 
series  device,  the  following  current  limitation 
applies: 

Voltage 

Max. Current 

48V DC 

0.75A  

6, 12 & 24V DC 

2.0A 

 
If a Zener diode module is pre-fitted as either EOL 
or  Series  device,  the  following  current  limitation 
applies: 

Zener 
Voltage 

Max. Input 
Voltage 

Max. Current 

3.3V 

56V DC 

230mA 

4.7V 

162mA 

5.1V 

149mA 

5.6V 

136mA 

6.2V 

122mA 

6.8V 

112mA 

10V 

76mA 

12V 

63mA 

 
In  any  scenario,  the  lowest  value  of  maximum 
current  should  be  used.  For  example,  if  the  unit 
has  both  a  diode  and  a  Zener  diode,  the  Zener 
diode  would  determine  the  maximum  input  current 
of the unit, since its max. current is lowest.  

8) 

Testing unit operation 

The  break  Glass  unit  can  be  tested  without  the 
need to break/replace the frangible glass element.  
A  test  key  is  used  to  mechanically  drop  the  glass 
down activating the switch. 

 

The test key is inserted in the test cam and rotated 
clockwise by an angle of 60º the glass element will 
visibly drop down in the viewable window. 
 
The  call  point  switch  will  now  change  over  its 
contacts to operate the alarm. 
Once  testing  is  complete  the  unit  needs  to  be 
reset, the test key is rotated back anticlockwise by 
an angle of 60º back to its original position. The  
glass  element  should  now  raise  up  so  it  is  level 
again in the viewable window. 
 

 

1. 

          2. 

             

3. 

Insert test            Hold in           

 Rotate back  

Key rotate            position          

 anticlockwise  

clockwise             during            

 to reset 

60º                        test 
 

9) 

Replacement of glass element 

If  the  break  glass  unit  has  been  operated  the 
broken glass element can be quickly replaced. 
The  break  glass  cover  plate  is  removed  by 
unscrewing the 4 off M4 cap head screws attaching 
it.  

Once  cover  is  removed  the  broken  glass  will  be 
free to be removed, clean out any other fragments 
of glass carefully. 

 

 
To  fit  the  new  glass  element  rotate  the  top  cam 
clockwise  by  an  angle  of  50º  (use  a  6mm  Allen 
key) this will than allow the glass to fit back into the 
pocket it sits in, resting  on the pivot  point and test 
cam, release the top cam to  rest on the top  of  the 
glass element. 
 
 

 

 
Pivot point     Test Cam    Top Cam (rotate) 
 
Replace  the  cover  plate  and  tighten  the  4  off  M4 
cap head screws. 
 
Ensure the glass element is free to move under the 
cover  plate.  This  can  be  done  by  running  through 
the  units  test  operation.  See  section  8  of  this 
instruction manual. 
 
 
 
 
 
 
 
 
 
 