Address
Loop Number
Device Zone
3
2
1
Enabled
New
Device State
More
Remove
OFF
Name
Save
The “MORE” menu can also be used to view the status of output channels CHANNEL 3 and CHANNEL 4.
There are two fields next to the channel label; the first lists output operating mode indications (monitored or relay) or a fault
indication:
• Type Error - an incorrect output type has been detected, i.e. a jumper has been closed/opened while the module is
powered. The fault will be reset when the module is disconnected from the Loop power supply and the output power
supply is disabled.
• Power Supply Fault: indicates a lack of external power supply at the outputs.
The second indicates the current status of the outputs, which may be one of the following:
• ON – the output is enabled.
• OFF – the output is not enabled.
• Open - the line connected to the output is open, or the end-of-line resistor is not connected.
• Short - there is a short-circuit in the line connected to the output. In the event of a short-circuit, when the monitored output
is triggered, the output power supply will be disabled until normal operating conditions are restored.
The input or output channel configuration may be programmed via “rapid activation” by directly pressing the button showing
the module model.
17/06/2020 14:06
Input
Channel 1
Name
Input
Channel 2
Name
Output
Channel 3
Name
Output
Channel 4
Name
To enter the input or output activation type, press the button alongside the Channel with the corresponding number and select
one of the options. A name of up to 40 characters can be assigned to each channel in the editable bar next to the “Name”
label”.
The configurable “rapid programming” options on input and output channels are the same as those listed in the
paragraph concerning addressed module 41IOM022.
To save any new parameters, press “Save” on the main device screen.