INSTALLATION AND MAINTENANCE INSTRUCTIONS  

 
Model FS-WST   

Addressable Wall Mount Strobe  

Notifier by Honeywell

9 Columbia Way Baulkham Hills,NSW 2153 

Australia

www.notifier.com.au

SPECIFICATION 

Item 

Parameter Description 

Note 

Operating Voltage 

DC24V( DC15V~ DC32V) 

 

Avg. Standby Current 

<400µA 

24VDC, No Communication, No flashing 

Alarm  Current 

<8mA 

Alert flash pattern(4.4mA) 

Evacuate flash pattern(4.6mA) 

Operating Temp 

-25

~+70

 

 

Humidity 10~95% 

R.H. 

Non-condensing 

Ingress Protection 

IP33  

IP35(With Water-proof box  ) 

 

Flash Pattem 

See table 1:  ‘Setting’  

Flash Intensity 

>1cd 

 

Height 47mm 

 

Diameter 122mm 

 

Weight 156

±

6g  

 

 
Before installing and using the product, please read the system 
wiring and installation manual thoroughly. If the products will 
be installed in an existing operational system, inform

 

the operator 

and local authority that the system will be temporarily out of 
service, disconnect

 

power to the control panel before installing the

products. 
NOTICE: This manual should be left with the owner/user of this 
equipment. 
 

GENERAL 

FS-WST is an intelligent addressable AV products designed to 
alarm light for emergency events, and be able to communicate
with control panel by intelligent protocol. 
It is designed specifically for analogue addressable fire alarm 
system and only can be connected to control panels with a 
compatible proprietary analogue addressable communication 
protocol. It is powered from the loop and can be controlled via 
the communication protocol(s). The Wall Mount Version is 
compatible with B501 mounting base. Up to 159 addresses are 
available via two rotary selector switches.  The alarm light can
be tested on field.  
 

INSTALLATION 

It must be installed and wired with B501 mounting base. 
1.

 

Verify the product type matches with product drawing. 

2.

 

Set the address via two rotary selector switches. Please
refer to “Address setting”. 

3.

 

Volume and tone setting are realized by 4 digit DIP witch. 
On field testing can be tested via DIP switch. 

4.

 

Plug the 

Wall Mount Strobe

 into B501 mounting base. 

5.

 

Turn the 

Wall Mount Strobe

 clockwise until it drops into

place. 

6.

 

Continue turning the 

Wall Mount Strobe

 clockwise to lock it 

in place. 
 
 
 
 
 

 
 

 
Figure 1 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

SETTING 

Address setting 
Rotary-decade switches are provided for setting the address
whose range is from 1 to 159. (Default address is 01). 
Address is set by turning the switches. 
Address is calculated as below formula: Address = TENS *10 
+ ONES*1. For instance: Address 05 = 0*10 + 5*1. 

A5665

006

B501 
Mounting 
Base 

Wall Mount 
Strobe 

I5

6

-59
21-
000

 