CONNECTION OF ANALOGUE OUTPUTS (2/2)
2. Separate power supply
This type of connection requires the use of two power supplies. The first connected to the optoisolated section of the ADM module and
the second to the load.
This solution is recommended when the load device requires high command signal precision. The 0 V must be earthed only on the
power supply connected to the load device.
The connection must be made only with a shielded cable or shielded twisted pair. The shield must be connected to
earth from the signal source side.
The cable used for the connection must be as short as possible.
Do not lay the cable close to high energy sources or in cable fairleads with other cables.
In the event of crossing other cables try to provide an intersection at right angles.
Do not lay the cable on surfaces subject to vibration.
Do not bend the cable with bending radii that are too small.
SIGNAL ALLOCATION
SIGNAL
RED
LED
CONN. J3 PIN
(MOD. FRONT)
CONN. X3X PIN
(CABINET BASE)
SIGNAL
RED
LED
CONN. J3 PIN
(MOD. FRONT)
CONN. X3X PIN
(CABINET BASE)
INPUT 1
A1
A1
A1
OUTPUT 1
C1
C1
C1
INPUT 2
A2
A2
A2
OUTPUT 2
C2
C2
C2
INPUT 3
A3
A3
A3
OUTPUT 3
C3
C3
C3
INPUT 4
A4
A4
A4
OUTPUT 4
C4
C4
C4
INPUT 5
B1
B1
B1
OUTPUT 5
D1
D1
D1
INPUT 6
B2
B2
B2
OUTPUT 6
D2
D2
D2
INPUT 7
B3
B3
B3
OUTPUT 7
D3
D3
D3
INPUT 8
B4
B4
B4
OUTPUT 8
D4
D4
D4
INP 1
¸
8 RET.
–
AR
A12
OUT. 1
¸
8 COM.
–
CC
C10
OUT. 1
¸
8 RET.
–
CR
C12
ANAL. OUT USER
POWER +24 Vdc
–
C7
C7
ANAL. OUT USER
P24Vdc)
–
C8
C8
ANALOG OUT 1-
–
A5
A16
ANALOG OUT 1+
–
A6
A15
SHIELD ANAL.
OUTPUT 1
–
A8
A14
ANAL. OUT 2-
–
B7
B16
ANAL. OUT 2+
–
B8
B15
SHIELD ANAL.
OUTPUT 2
–
B5
B14
OUTPUT PROT.
FUSE
FUSE
–
–
C3G
Plus
INTEGRATION GUIDE
00/1097
4-33
parallel
i/o
C3G-ADM
Summary of Contents for C3G Plus
Page 6: ...This page has been intentionally blank UPDATING LIST C3G Plus D 08 0702 ...
Page 14: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 24: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 26: ...This page has been left intentionally blank INSTALLATION C3G Plus 2 ii 01 0498 SUMMARY ...
Page 48: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 122: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 127: ...C3G Plus INTEGRATION GUIDE 06 0400 4 5 SYSTEM I O ...
Page 160: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 182: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 188: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 190: ...This page has been left intentionally blank MAINTENANCE C3G Plus 7 ii 00 1097 GENERAL RULES ...
Page 225: ...X30 connector test device C3G Plus MAINTENANCE 01 0498 7 35 diagnostic ...
Page 264: ...This page has been intentionally blank 7 74 08 0702 MAINTENANCE C3G Plus LIST OF SPARE PARTS ...
Page 265: ...OPERATOR S NOTES C3G Plus NOTES ...
Page 266: ...C3G Plus NOTES ...