C3G-ACI
32 AC INPUT MODULE
VME Input module compatible with 110 Vac 32 channel slave type interface, with signalling through activation of LEDs on front panel
when an input is present.
It may be added on the Control Unit rack starting from the first free slot at the right of the basic configuration modules.
TECHNICAL CHARACTERISTICS
INPUT
Number of inputs
32
Number of common returns (0 V)
4
Input voltage for channel activation
79.0 to 132.0 Vac
Input voltage for channel deactivation
0.0 to 20.0 Vac
Input current with channel activated
4.0 to 15.0 mA
Maximum input current with channel not activated
1.5 mA
Operating frequency
47 to 63 Hz
SIGNAL ALLOCATION
SIGNAL
RED
LED
CONN. J3 PIN
(MOD. FRONT)
CONN. X3X PIN
(CABINET BASE)
SIGNAL
RED
LED
CONN. J3 PIN
(MOD. FRONT)
CONN. X3X PIN
(CABINET BASE)
INPUT 1
A1
A1
A1
INPUT 17
C1
C1
C1
INPUT 2
A2
A2
A2
INPUT 18
C2
C2
C2
INPUT 3
A3
A3
A3
INPUT 19
C3
C3
C3
INPUT 4
A4
A4
A4
INPUT 20
C4
C4
C4
INPUT 5
A5
A5
A5
INPUT 21
C5
C5
C5
INPUT 6
A6
A6
A6
INPUT 22
C6
C6
C6
INPUT 7
A7
A7
A7
INPUT 23
C7
C7
C7
INPUT 8
A8
A8
A8
INPUT 24
C8
C8
C8
INPUT 9
B1
B1
B1
INPUT 25
D1
D1
D1
INPUT 10
B2
B2
B2
INPUT 26
D2
D2
D2
INPUT 11
B3
B3
B3
INPUT 27
D3
D3
D3
INPUT 12
B4
B4
B4
INPUT 28
D4
D4
D4
INPUT 13
B5
B5
B5
INPUT 29
D5
D5
D5
INPUT 14
B6
B6
B6
INPUT 30
D6
D6
D6
INPUT 15
B7
B7
B7
INPUT 31
D7
D7
D7
INPUT 16
B8
B8
B8
INPUT 32
D8
D8
D8
INPUT 1
¸
8 RET.
–
AR
A12
INP. 17
¸
24 RET.
–
CR
C12
INPUT 9
¸
16 RET.
–
BR
B12
INP. 25
¸
32 RET.
–
DR
D12
FUSE (NOT USED)
FUSE
–
–
C3G
Plus
INTEGRATION GUIDE
00/1097
4-25
parallel
i/o
C3G-ACI
EXAMPLE OF CONNECTION
Summary of Contents for C3G Plus
Page 6: ...This page has been intentionally blank UPDATING LIST C3G Plus D 08 0702 ...
Page 14: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 24: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 26: ...This page has been left intentionally blank INSTALLATION C3G Plus 2 ii 01 0498 SUMMARY ...
Page 48: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 122: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 127: ...C3G Plus INTEGRATION GUIDE 06 0400 4 5 SYSTEM I O ...
Page 160: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 182: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 188: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 190: ...This page has been left intentionally blank MAINTENANCE C3G Plus 7 ii 00 1097 GENERAL RULES ...
Page 225: ...X30 connector test device C3G Plus MAINTENANCE 01 0498 7 35 diagnostic ...
Page 264: ...This page has been intentionally blank 7 74 08 0702 MAINTENANCE C3G Plus LIST OF SPARE PARTS ...
Page 265: ...OPERATOR S NOTES C3G Plus NOTES ...
Page 266: ...C3G Plus NOTES ...