OUTPUT SIGNALS TOWARDS EXTERNAL LOGIC (MACHINE LINE)
These are controller output signals used to communicate with external equipment (e.g. a PLC).
PIN
X30
SIGNALS
DESCRIPTION
8
DRIVE ON/OFF
(LED C1 SIM, $SDOUT[9])
When closed indicates that the control unit has received the
Drive ON command from the machine line, has carried out
the motor start-up procedure and is in Drive ON status.
(Drive ON = true, Drive OFF = false)
26
START/HOLD
(LED C2 SIM, $SDOUT[10])
When closed, it means that control unit has received
START signal with at least one "HODABLE" program pre-
viously activated and ready to start.
9
27
10
28
U1 (LED C3 SIM, $SDOUT[13])
U2 (LED C4 SIM, $SDOUT[14])
U3 (LED C5 SIM, $SDOUT[15])
U4 (LED C6 SIM, $SDOUT[16])
Undefined
output
signals
whose
function
can
be
customised through user programming.
11
LOCAL/REMOTE
(LED C7 SIM, $SDOUT[11])
When closed indicates that the remote operating mode
has been selected using the status selector on the front
panel and that the system is in Remote status.
(Local = false, Remote = true)
29
ALARM (LED D1 SIM, $SDOUT[4])
When open indicates that an alarm has occurred and has
been detected by the control unit.
(no alarm = true, alarm = false)
12
TEACH EN/DIS
(LED C8 SIM, $SDOUT[12])
When closed indicates that the system is in Programming
status (through selection on front panel) and has enabled
the relevant safety devices (reduced speed, servo alarm
threshold restriction).
13
AUTO/MAN PTU ($SDOUT[17])
When closed indicates that the AUTO/MAN selector on
the programming terminal is in the AUTO position, i.e.
programming operations involving robot movement are
performed at machine working speed.
(Auto = true, Man = false)
30
EMERG. STOP TO REMOTE
Emergency signal to remote which is opened when one of
the emergency buttons on the programming terminal or
operator panel is pressed (normally closed).
14
32
COMMON 24 Vdc
+ 24 Vdc common return reference for output signals.
25
OUTPUT COMMON RETURN 0 Vdc
0 Vdc common return reference for output signals.
71
COMMON (STATUS SELECTOR)
Common wire for auxiliary contacts.
54
PROGRAMMING
Status selector in programming position
42
AUTO-LOCAL
Status selector in automatic-local position
40
AUTO-REMOTE
Status selector in automatic-remote position
C3G
Plus
INTEGRATION GUIDE
04/0799
4-7
SYSTEM
I/O
Summary of Contents for C3G Plus
Page 6: ...This page has been intentionally blank UPDATING LIST C3G Plus D 08 0702 ...
Page 14: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 24: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 26: ...This page has been left intentionally blank INSTALLATION C3G Plus 2 ii 01 0498 SUMMARY ...
Page 48: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 122: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 127: ...C3G Plus INTEGRATION GUIDE 06 0400 4 5 SYSTEM I O ...
Page 160: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 182: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 188: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Page 190: ...This page has been left intentionally blank MAINTENANCE C3G Plus 7 ii 00 1097 GENERAL RULES ...
Page 225: ...X30 connector test device C3G Plus MAINTENANCE 01 0498 7 35 diagnostic ...
Page 264: ...This page has been intentionally blank 7 74 08 0702 MAINTENANCE C3G Plus LIST OF SPARE PARTS ...
Page 265: ...OPERATOR S NOTES C3G Plus NOTES ...
Page 266: ...C3G Plus NOTES ...