InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
47
I00
Not Used
Input has no function. Use this configuration when binary or analog input is not connected.
Hint:
is input-output terminal. Primarily it is configured as an output. To configure as an input,
O00 Not Used
in the output configuration.
I01
Emergency Stop
This input will activate the built-in
alarm. It is recommended to use a
If this binary input is activated, the left red LED above
Stop
button will blink, the general shutdown
symbol will be dis
played on LCD’s upper right corner,
symbol will be displayed on
event log with running hours stamp and shut down procedure will occur. For more details see
Shutdown procedure in chapter
12 Alarm, Events and History Management.
C
AUTION
!
This is a software function only.
I02
Remote Start/Stop
9.2.1
This input is an external request for engine run. It is active in
Auto
mode only.
In MRS mode the controller starts the engine and keeps GCB open.
In AMF mode the controller starts the engine and keeps GCB open. Only when mains fail occur GCB
is automatically closed.
N
OTE
:
The
Remote Start/stop
can be configured only on terminal
This is also used for waking the
controller from “Zero Power” mode.
I03
Remote Start And Load
9.2.2
The
Remote Start And Load
input can be used only when the controller is in
Auto
mode.
In AMF mode this input starts the engine and transfers the load to the generator after all engine and
generator parameters are within tolerance (open MCB and close GCB). When this input is
deactivated the controller will transfer the load back to mains and stop the engine.
In MRS mode this input starts engine and closes the GCB (only when is configured). When this input
is deactivated the controller will open the breaker (only when is configured) and stop the engine.
N
OTE
:
The
Remote Start And Load
can be configured only on terminal
. This is also used for waking
the controller from “Zero Power” mode.