InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
68
E15 Fuel Level Shutdown
Units:
%
Step:
1
Range:
0 - 20
Default value:
10
When this protection is activated the red LED above
Stop
button will blink, the general shutdown
symbol will be displayed on LCD’s upper right corner. Fuel Level SD symbol will be displayed on event
log with running hours stamp and the shutdown procedure will occur.
Input has 10s delay.
E06
Battery Undervoltage
Units:
Volts [V]
Step:
0,1 V
Range:
8
– 40 V
Default value:
11,5 V
Delay:
30 s
Warning threshold for
E07 Warning Maintenance
Units:
hours [h]
Step:
1 h
Range:
0
– 10000 h
Default value:
9999 h
Counts down when the engine is running. When the counter reaches zero, an alarm will appear.
When the value 10000 is set, than the Maintenance function is disabled and counter will not count.
Counter value will not appear in the controller’s statistics. Maximum value for running countdown is
9999.
will appear when counter time has elapsed.
E08 Oil Pressure Starter Disengagement
Units:
Step:
Range:
1,2
Default value:
1
When this setpoint is enabled, the controller will use
or
signal for starter disengagement. Starter will disengaged when oil pressure reach starting oil pressure
or binary input
will be opened (
contact) or closed (
When is disabled then only RPM (frequency), generator voltage or D+ will be used for starter
disengagement.
Setpoint code
Value
Meaning
E08
1
Disable
E08
2
Enable