InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
73
A
– AMF (Auto Mains Failure) settings
10.4
A01 Emergency Start Delay
Units:
seconds [s]
Step:
1 s
Range:
0
– 600 s
Default value:
5
Delay between the mains failure and the automatic start of the gen-set to an AMF operation.
A02 Mains Return Delay
Units:
seconds [s]
Step:
1 s
Range:
1
– 3600 s
Default value:
20 s
This is a "mains stabilization" time. Timer begins when mains returns. If the mains are continuously
healthy for this period, the controller will finish the AMF operation.
A03 Mains Overvoltage
Units:
percentage [%]
Step:
1 % of nominal system voltage
Range:
– 150%
Default value:
110 %
Delay:
0,1 s
Threshold for detection of mains failure due to overvoltage. The setpoint is adjusted relative to the
nominal system voltage (setpoint
depending on
A04
Mains Undervoltage
Units:
percentage [%]
Step:
1 % of nominal system voltage
Range:
50
Default value:
60 %
Delay:
0,1 s
Threshold for detection of mains failure due to overvoltage. The setpoint is adjusted relative to the
nominal system voltage (setpoint
depending on