InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
67
E - Engine parameters and protections
10.2
E01
Prestart Time
Units:
seconds [s]
Step:
1s
Range:
0-600s
Default value:
2
Time of closing of the
output prior to the engine start.
Set to zero if you want to leave the output
E02
Maximum Cranking Time
Units:
seconds [s]
Step:
1s
Range:
0-60s
Default value:
5
Maximum duration when the starter motor is energized.
E03 Cooling Time
Units:
seconds [s]
Step:
1s
Range:
0-3600s
Default value:
30
Runtime of the unloaded gen-set to cool the engine before stop.
E04 Oil Pressure Shutdown
Units:
Bar [Bar]
Step:
0,1 Bar
Range:
0-10 Bar
Default value:
1 Bar
Delay:
3 s
Shutdown threshold level for
I23 Oil Pressure Analog
input.
E05 Coolant Temperature Shutdown
Units:
degree Cels
ius [°C]
Step:
1 °C
Range:
0 -
150 °C
Default value:
90 °C
Delay:
5 s
Shutdown threshold level for
I25 Coolant Temperature Analog
input.