InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
61
B - Basic settings
10.1
B01
Nominal Voltage Ph-N
Units:
Volts [V]
Step:
1V
Range:
80
– 480 V
Default value:
230V
Nominal system voltage (phase to neutral). This setpoint can be hidden depending on the connection
type (setpoint
). You can setup this value only if you will choose the connection
type as Mono phase or Split phase -
(1; 2).
B02
Nominal Voltage Ph-Ph
Units:
Volts [V]
Step:
1V
Range:
80
– 600 V
Default value:
400V
Nominal system voltage (phase to phase). This setpoint can be hidden depending on the connection
type (setpoint
).You can setup this value only if you will choose the connection
type as 3Ph3Wire or 3Ph4Wire -
(3; 4).
B03
Nominal Frequency
Units:
Step:
Range:
1,2
Default value:
1
Nominal system frequency.
Setpoint code
Value
Meaning
B03
1
50Hz
B03
2
60Hz