O00 Not Used
Output has no function. Use this configuration when output is not connected.
O01 Starter
This output is dedicated for starter motor control. The number of cranking attempts is 6.
Prestart Time
0 - 600 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Gen-set start failed
On
Off
Start
Starter Output
Time
6 Cranking Attempts
Prestart Time
Maximum
Cranking Time
0 - 60 s
Gen-set start failed – shutdown,
if the voltage or frequency are not in
the limit
On
Off
Time
Start
Engine run
Max. Stab. Time 7 s
Min. Stab. Time
Starter Output
The starter output become inactive when one of following conditions is reach or exceeded.
RPM
≥ 25% of nominal RPM (1500RPM=50Hz; 1800RPM=60Hz)
or
≥ 3 bar (43 PSI), only when
Oil Pressure Starter Disengagement
or
input is opened, only when
Oil Pressure Starter Disengagement
or
voltage on D+ terminal ≥ 80% of battery voltage for 1 s or longer