InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
85
7.4.27 100%ofSpeedReq
[RPM]
Limit for Speed Request transformation from RPM to % range for ECU engines using % format.
Step:
1RPM
Range:
0 - 4000RPM
Default:
2000RPM
7.4.28 Conveyor horn
[s]
Horn time before the conveyor output starts.
Step:
1s
Range:
0 - 600s
Default:
7s
7.4.29 Running timer
[min]
Automatic engine stop in MAN mode or delayed engine stop in AUT mode. Start engine in MAN mode
by START button. Engine stops itself after
Running Timer
is over. Engine stays running when
Running
Timer =
0
Step:
1min
Range:
0 - 1000min
Default:
0min
7.4.30 FuelTankVolume
[L]
This setpoint is describing volume of fuel tank for counting fuel consumption depending on Fuel level
drop.
Step:
1L
Range:
0
– 10000L
Default:
200L
7.4.31 MaxFuelDrop
[%/h]
This is setting protection against the fuel leakage or theft.
Function monitors the AIN3 Fuel level value in percentage scale without decimals. The alarm and
history record “Wrn FuelTheft” is activated when Fuel level change is faster than setpoint limit.
Function is switched off when Max Fuel Drop = 0 %/h.
The drop out limit on stopped engine is 5% to avoid unwanted Alarm activation due to AIN3: Fuel level
fluctuations.
Active alarm "Wrn FuelTheft" can be sent via SMS and displayed by WebSupervisor (if used).
Step:
1
Range:
0 - 50%
Default:
25%
H
INT
Set 0 to disable Fuel Theft Protection function into MaxFuelDrop setpoint.