InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
57
State
Condition of the transition
Action
Next state
OFF mode selected or Shut down alarm
active
Not Ready
Not Ready RPM < 2, Oil pressure not detected, D+
not Active, no shutdown alarm active,
other than OFF mode selected
Ready
Prestart
1
Prestart time
elapsed
STARTER
on
FUEL SOLENOID
on
2
MaxCrank
time
counter
started
Cranking
Cranking
1
RPM
> Start RPM AND BI: Nominal/Idle
is active
STARTER
off
PRESTART
off
Starting
RPM >
Start RPM
AND BI: Nominal/Idle
is
not
active
STARTER
off
PRESTART
off
READY TO LOAD
on
Running
D+ input activated for 1s or oil pressure
detected
STARTER
off
PRESTART off
Cranking
MaxCrank time
elapsed, 1st attempt
STARTER
off
FUEL SOLENOID
off
STOP
SOLENOID
on
CrankFail pause
timer started
Crank pause
MaxCrank time
elapsed, last attempt
STARTER
off
PRESTART
off
Shutdown
(Start
fail)
Crank
pause
1
CrankFail pause
elapsed
STARTER
on
FUEL
SOLENOID
on
2
STOP SOLENOID
off
MaxCrank
time
counter
started
Cranking
Starting
1
BI: Nominal/Idle
is active
FUEL
SOLENOID
on
2
STOP SOLENOID
off
READY TO LOAD
off
Starting
RPM = 0 or any other shutdown
condition
FUEL SOLENOID
off
STOP SOLENOID on
Shutdown
60 sec.
Elapsed
FUEL SOLENOID
off
STOP SOLENOID on
Shutdown
(Start
fail)
Running
Stop request
READY TO LOAD off
Cooling time
timer started
Cooling