InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
122
10.2.4 Stop solenoid
The closed output energizes stop solenoid to stop the engine.
The output is active at least for
Stop time
, if the stop lasts longer; it stays active until all symptoms say
the engine is stopped.
The engine is stopped if:
RPM < 2 and
Oil pressure <
Engine params
:
StartingPoil
H
INT
The engine can be started anytime, if all symptoms say the engine is steady regardless of the fact the
Stop solenoid
can still be active (in that case it is deactivated before cranking).
10.2.5 Stop Pulse
Output is active for 1 second after
Stop solenoid
output activation. This signal is sent to ECU in case
of engine stop request.
10.2.6 Ignition
The output closes after reaching value of CrankRPM, fixed 30RPM. The output opens after stopping of
the engine or in pause during repeated start.
10.2.7 Prestart
The output closes prior to the engine start (
Prestart
) and opens when
Starting RPM
speed is reached.
During repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
10.2.8 Preglow
The output closes prior to the engine start and opens when
Starting RPM
speed is reached. During
repeated crank attempts the output is closed too.
The output could be used for pre-glow or pre-heat.
10.2.9 Cooling pump
The output closes when engine starts and opens after
Engine params
the engine
10.2.10 Idle/Nominal
binary input or I/O button in MAN mode or follows the
engine state in AUT mode:
The
output
Idle/Nominal
closes after the timer
Idle time
elapses. The
Idle time
counter starts to
countdown when
Start speed
reached. The
Underspeed
protection is not evaluated during idle time.
Start fail
protection occurs if the RPM drop below 2RPM during idle state.
H
INT
When LBI Nominal/Idle is configured (to a physical binary input), it has priority and the switching
between the nominal and the idle speed by I/0 button is blocked.