InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
80
7.4.10 Cooling speed
[IDLE, NOMINAL]
Selects the function of the Binary output IDLE/NOMINAL during engine Cooling state.
IDLE:
Cooling is executed at Idle speed.
NOMINAL:
Cooling is executed at Nominal speed. Default state.
H
INT
Binary output IDLE/NOMINAL must be configured and connected to speed governor. Engine Idle
speed must be adjusted on speed governor.
7.4.11 Cooling time
[s]
Run time of the unloaded engine to cool the engine before stop.
Step:
1s
Range:
0 - 3600s
Default value: 30s
7.4.12 AfterCool time
[s]
Run time of engine after cooling pump. Binary output
Cooling pump
is closed when the engine starts
and opens
AfterCool time
delayed after engine stops.
Step:
1s
Range:
0 - 3600s
Default value: 180s
7.4.13 Stop time
[s]
Under normal conditions the engine must certainly stop within this period. The period starts by issuing
stop command.
Step:
1s
Range:
0 - 240s
Default value: 60s
H
INT
Stop of engine is detected when all following conditions are met: RPM <2, Oil pressure <
StartingPOil
and D+ input isn’t active.
Stop fail is detected if there is difference between those conditions.
7.4.14 Fuel solenoid
[DIESEL, GAS]
Setpoint setting determines behavior of the Binary output FUEL SOLENOID.
DIESEL:
Output closes 1 sec before Binary output STARTER.
The output opens if Emergency stop comes or Cooled engine is stopped and in pause
between repeated starts.
GAS:
In this mode of operation the output closes to open the gas valve and enable the
engine to start. The delay of Fuel solenoid output activation in relation to Starter output
is defined by
FuelSol offset
. The output closes only if RPM > 30 (i.e. the starter motor
is engaged).