7.8.3 Time
[HH:MM:SS]
Actual time.
7.8.4 Date
[DD:MM:YYYY]
Actual date.
7.8.5 Timer1Function
[NoFunc,
AutoRun,
AutoRegCMP,
AutoBatt,
AutoStop]
No Func:
Operates just corresponding LBO Timer1 according the Timer1 setting, see
Timer1
repeat
,
Time1 ON time
,
Timer1Duration
. Function operates in all OFF-MAN-AUT
modes.
Default
state.
AutoRun:
Engine automatically starts and stops in AUT mode (similar to LBI Rem start/stop, the
same
record
in
the
history)
according
the
Timer1
setting.
AutoRegCMP: Start and stop engine in AUT mode according to the LBO Speed switch - see
Regulator
:
Reg CMP
setpoints. The comparator function (output) works opposite
when
Regulator
:
Reg CMP On
<
Reg CMP Off
. The
Date/Time
:
Timer1 repeat
,
Timer1
ON time
,
Timer1Duration
settings are not important in this case.
AutoBatt:
Engine starts when actual Battery voltage <
Engine protect:
Batt und Batt volt
del and stays running for
Date/Time:
Timer1 Duration. Function operates in AUT
mode.
AutoStop:
Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like by
STOP button) when engine runs longer then
Date/Time:
Timer1Duration on actual
RPM less or equal
Engine params:
Idle speed + 5% (fix limit). Function is not active
during engine start.
7.8.6 Timer1repeat
[NONE, MONDAY, TUESDAY, WEDNESDAY,
THURSDAY,
WEDNESDAY,
FRIDAY,
SATURDAY, SUNDAY, MON-FRI, MON-SAT,
MON-SUN, SAT-SUN]
This setpoint defines Timer1 activation. Binary output Timer1 is internally linked with Rem Start/Stop
binary input. Refer to binary inputs for details.
NONE:
Timer function is disabled. Defualt state.
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
Timer is activated on daily basis.
MON-FRI, MON-SAT, SAT-SUN:
Timer is activated on selected day interval.
7.8.7 Timer1 ON time
[HH:MM:SS]
Display day time when Timer 1 output is activated.
7.8.8 Timer1Duration
[min]
Adjusts duration of Timer 1 output.