InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
75
H
INT
When opening connection to the controller its address has to correspond with the setting in PC tool.
7.3.2 COM1 Mode
[DIRECT/MODEM/MODBUS/ECU LINK]
Communication protocol switches for the COM1 channel.
DIRECT:
LiteEdit communication protocol via direct cable or AirGate, WebSupervisor
communication protocol via AirGate.
MODEM:
LiteEdit communication protocol via modem.
MODBUS:
Modbus protocol. See detailed description in InteliDrive Communication Guide.
ECU LINK:
Protocol for communication with Cummins engines via Modbus.
H
INT
For details on communication speed and other technical parameters please see chapter Technical
Data.
For detail description see chapter Modbus protocol.
7.3.3 COM2 Mode
[DIRECT/MODBUS/ECU LINK]
Communication protocol switches for the COM2 channel, if dual communication module is plugged in.
DIRECT:
LiteEdit communication protocol via direct cable.
MODBUS:
Modbus protocol. See detailed description in InteliDrive Communication Guide
ECU LINK:
Protocol for communication with Cummins engines via Modbus.
H
INT
For details on communication speed and other technical parameters please see chapter Technical
Data.
For detail description see chapter Modbus protocol.
7.3.4 ModemIniString
[-]
In case that your modem needs additional initialization e.g. AT commands, it can be entered here.
Otherwise leave this setpoint blank.
7.3.5 ModbusComSpeed
[9600, 19200, 38400, 57600]
If the Modbus mode is selected on COM1 or COM2 channels, the Modbus communication speed in
bps
can be adjusted here.
H
INT
In case of ModBus/TCP communication via IB-Lite communication module is automatically adjusted
COM1 Mode=DIRECT, COM2=MODBUS and ModbusComSpeed=57600. T
here isn’t required any
other additional setting (of course except IB-Lite setpoints, see below)
7.3.6 IBLite IP Addr
[-]
IP address of IB-Lite module
7.3.7 IBLite NetMask
[-]
IB-Lite network mask