7.2.7 ControllerMode
[OFF, MAN, AUT]
Equivalent to Controller mode changes by MODE
or
MODE buttons.
H
INT
Controller Mode change can be separately password protected.
7.2.8 FltResGoToMAN
[ENABLED, DISABLED]
DISABLED:
Controller stays in AUT mode after Fault reset. Default state.
ENABLED:
Automatic switch from AUT to MAN mode after Fault reset to avoid automatic engine
start. This function is active for Shut down protection only.
7.2.9 DispBacklightTO
[min]
The display backlight is switched off after timeout.
Step:
1min
Range:
0 - 60min
Default value:
0 … means that the display lights all the time
7.2.10
Panel Button
[Nom/Idle,
N/I
Init,
Conveyor,
RegReqst,
R
RegDis,
CloseLoad,
Toggle]
Adjust the function of front panel button I/O.
Default state:
Nom/Idle
Nom/Idle:
Switches between Nominal and Idle speed request. The function is allowed in MAN
mode only, after reaching the status RUN and the requsted speed set by the setpoint
ECU SpeedAdj
. (i.e. not during IDLE speed warm-up run in Starting status).
N/I Init:
Switching between Nominal and Idle speed request. After the starting, the speed
according to the setpoint
Idle Speed
is reached and this status is maintained until the
I/0 button is pressed. The function is allowed in MAN mode only and is blocked during
Cooling time.