Under limit
Protection is activated only when measured value is under measured level.
Over limit
Protection is activated only when measured value is over measured level.
Undfls
Level 2 protection is activated by sensor fail too.
Ovfls
Level 2 protection is activated by sensor fail too.
7.11 SMS/E-Mail
H
INT
If a cellular network modem and/or internet bridge is connected to the controller, the controller can
send SMS messages and/or emails in the moment when a new alarm appears in the Alarm list. The
message will contain a copy of the Alarm list.
To enable this function, you should select with setpoints
Yel Alarm Msg
and
Red Alarm Msg
, which
levels of alarms shall be announced (red/yellow/both) and also enter valid cellular network phone
number and/or e-mail address to the setpoints
TelNo/Addr Ch1
and
TelNo/Addr Ch2
. It is possible to
put either number or e-mail to both setpoints.
N
OTE
:
An internet module must be available for sending of e-mails. Similarly, a cellular network modem is
necessary for sending of SMS.
H
INT
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120
sec controller starts the next attempt. During the time the IL-NT-GPRS is trying to send an active call
type, incoming calls are blocked.
7.11.1 Yel Alarm Msg
[OFF, ON]
Set this setpoint to YES if you want to get messages when a
yellow
(warning) alarm occurs.
H
INT
The target address (cellular network phone number or e-mail address) must be set correctly to the
setpoint(s)
TelNo/Addr Ch1
resp.
TelNo/Addr Ch2
.
7.11.2 Red Alarm Msg
[OFF, ON]
Set this setpoint to YES if you want to get messages when a
red
(shutdown) alarm occurs.
H
INT
The target address (cellular network phone number or e-mail address) must be set correctly to the
setpoint(s)
TelNo/Addr Ch1
resp.
TelNo/Addr Ch2
.
7.11.3 TelNo/Addr Ch1, 2
[…]
Enter either a valid cellular network phone number or e-mail address to this setpoint, where the alarm
messages shall be sent. Type of active call is considered from the value of this parameter. If it consist
„@“ it is supposed to be e-mail address and active e-mail is sent. If the value is number, without „@“, it