InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
108
Step:
1min
Range:
1 - 1440min
Default:
5min
7.8.9 Timer2Function
[NoFunc,
AutoRun,
AutoRegCMP,
AutoBatt,
AutoStop]
No Func:
Operates just corresponding LBO Timer2 according the Timer2 setting, see
Timer2
repeat
,
Time2 ON time
,
Timer2Duration
. Function operates in all OFF-MAN-AUT
modes.
Default
state.
AutoRun:
Engine automatically starts and stops in AUT mode (similar to LBI Rem start/stop, the
same
record
in
the
history)
according
the
Timer2
setting.
AutoRegCMP: Start and stop engine in AUT mode according to the LBO Speed switch - see
Regulator
:
Reg CMP
setpoints. The comparator function (output) works opposite
when
Regulator
:
Reg CMP On
<
Reg CMP Off
. The
Date/Time
:
Timer2 repeat
,
Timer2
ON time
,
Timer2Duration
settings are not important in this case.
AutoBatt:
Engine starts when actual Battery voltage <
Engine protect:
Batt und Batt volt
del and stays running for
Date/Time:
Timer2 Duration. Function operates in AUT
mode.
AutoStop:
Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like by
STOP button) when engine runs longer then
Date/Time:
Timer2Duration on actual
RPM less or equal
Engine params:
Idle speed + 5% (fix limit). Function is not active
during engine start.
7.8.10
Timer2repeat
[NONE, MONDAY, TUESDAY, WEDNESDAY,
THURSDAY,
WEDNESDAY,
FRIDAY,
SATURDAY, SUNDAY, MON-FRI, MON-SAT,
MON-SUN, SAT-SUN]
This setpoint defines Timer2 activation. Binary output Timer2 is internally linked with Rem Start/Stop
binary input. Refer to binary inputs for details.
NONE:
Timer function is disabled. Defualt state.
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
Timer is activated on daily basis.
MON-FRI, MON-SAT, SAT-SUN:
Timer is activated on selected day interval.
7.8.11 Timer2 ON time
[HH:MM:SS]
Display day time when Timer 2 output is activated.
7.8.12 Timer2Duration
[min]
Adjusts duration of Timer 2 output.
Step:
1min
Range:
1 - 1440min