InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
117
9.3.8 Remote AUT
If the input is active, AUT mode is forced to the controller independently on the position of the MODE
selector. If another of remote inputs is active, then the Remote AUT input has the lowest priority.
9.3.9 RemControlLock
If the input is active, setpoints writing or command sending from the external terminal is disabled.
9.3.10 Emerg. manual
If the input is activated the controller behaves like when switched to OFF mode and opens all binary
outputs. There is one exception
– Stop solenoid doesn’t activate on this transition.
Detection of running engine and subsequent alarm message "Sd Stop fail" is blocked.
The controller shows “Emerg Man” state and the engine can not be started.
After the input is open again, the controller recovers to previous state and behaves according to the
actual situation.
Function is active in any controller mode.
9.3.11 StartButton
Binary input has the same function as Start button on the InteliDrive Lite front panel. It is active in
MAN mode only.
9.3.12 StopButton
Binary input has the same function as Stop button on the InteliDrive Lite front panel. It is active in
MAN mode only.
9.3.13 FaultResButton
Binary input has the same function as Fault reset button on the InteliDrive Lite front panel.
9.3.14 HornResButton
Binary input has the same function as Horn reset button on the InteliDrive Lite front panel.
9.3.15 Nominal/Idle
Input works in MAN mode only switching between running states Nominal/Idle. Active Nominal/Idle
input activates binary output
Idle/Nominal
and sends Speed request =
Engine params:
Idle speed
and/or active (binary) IDLE command to the ECU (e.g. to Volvo EMS).
Eng.state Sped request in MAN mode
Sped request in AUT mode
Idle
Engine params: Idle speed
Engine params: Idle speed
Running
Engine params: ECU SpeedAdj
… anything within
Engine params: MinSpeedLim
Engine params: MaxSpeedLim