Default:
0.0RPM
BI3
RPM IN
Basic settings:
Gear BoxRatio
0
0,1 to 5,0
Engine protect:
RPM diff Sd
RPM diff Wrn
RPM diff Del
GearBoxRatio=0
GearBoxRatio=0,1 to 5,0
RPM-BI3 Underspeed
GearBox check
Basic settings:
Gear Teeth3
Basic settings:
Gear Teeth
RPM
RPM-BI3
Engine protect:
RPM diff Sd
RPM diff Wrn
RPM diff Del
Engine
Gear box
RPM
RPM-BI3
H
INT
The RPM-BI3 measuring and corresponding protections are switched off when
Basic setting
:
GearTeethBI3
= 0. In this case BI3 operates as standard Binary input.
7.7.69 RPMdiff Sd
[RPM]
RPM-BI3 Sd underspeed protection limit or Sd difference limit between RPM-BI3 and RPM transferred
via GearBoxRatio. See description in GearBoxRatio setpoint. In alarm list appears text Sd RPMdiff.
Step:
1RPM
Range:
1 - 1000RPM
Default:
1000RPM
7.7.70 RPMdiff Wrn
[RPM]
RPM-BI3 Wrn underspeed protection limit or Wrn difference limit between RPM-BI3 and RPM
transferred via GearBoxRatio. See description in GearBoxRatio setpoint. In alarm list appears text
Wrn RPMdiff
Message: Wrn RPMdiff
Step:
1RPM
Range:
1
– 1000RPM
Default:
1000RPM
7.7.71 RPMdiff delay
[s]
Delay for RPMdiff protections above. See description in GearBoxRatio setpoint.
Step:
1s
Range:
0 - 600s
Default:
5s
7.7.72 BIN1 Prot Del
…BIN7 Prot Del [s]
Seven setpoints are dedicated for separately adjustment of the delay for each of binary inputs
according to the Class B protection standard.