IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
98
Force value
possible
YES
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as
Force block #3
are started to be
evaluated.
Setpoint: ResetActAlarms
Group
Engine protect
Range [units]
[-]
Related FW
3.0
Description
DISABLED
Pressing of the fault reset button (at any terminal or external
button) resets only
inactive
alarms. Active alarms remain in
the alarmlist unchanged and must be reset again when they
become inactive.
ENABLED
Pressing of the fault reset button (at any terminal or external
button) resets
all
alarms that are currently present in the alarm
list. Inactive alarms disappear from the alarm list immediately,
active alarms are changed to "confirmed" state and disappear
when the alarm condition disappear or the alarm starts to be
blocked.
N
OTE
:
ENABLED position corresponds to the method how the IG-classic and IS-classic
controllers handled the alarms.
Group: Analog protect
Setpoint: Batt >V
Group
Analog protect
Range [units]
8.0 .. 40.0 [V]
Related FW
3.0
Description
This setpoint adjusts the warning level for battery overvoltage alarm.
Setpoint: Batt <V
Group
Analog protect
Range [units]
8.0 .. 40.0 [V]
Related FW
3.0
Description
This setpoint adjusts the warning level for battery undervoltage alarm.