Description
This output is active if there is at least one
unconfirmed
2nd-level (red) alarm
present in the alarm list. See the chapter
Alarm management
for more
information.
Binary output: Cooling Pump
Related FW
3.0
Description
This output is used for control of an external electric motor-driven cooling pump.
The output closes when the gen-set is started (i.e. at the end of the
Starting
period) and opens at the end of the
Aftercooling
period, which takes place after
the engine has been fully stopped. Duration of the aftercooling period is adjusted
by the setpoint
AfterCool time
.
The output opens immediately when
controller is switched to OFF mode.
Binary output: BCB Close/Open
Related FW
3.0
Description
This output is intended for control of the BCB if a
contactor
is used as BCB. The
output provides continuous signal while the BCB has to be closed.
There are also other outputs availabe for BCB control:
•
•
•
T
IMING OF BREAKER CONTROL OUTPUTS