IGS-NT-BC, SW Version 1.2.0,   

©ComAp – January 2019                                                          

IGS-NT-BC-1.2.0 Reference Guide.PDF

 

 

37 

 

History Related functions 

History Records Adjustment 

It is possible to change History records content. Each record contains date, time and cause of the record as 
obligatory columns. The rest of columns are configurable. 
The history record structure has two parts. The upper part is so-called fast and is written into the history 
memory immediately in the moment when the written event occurs. The rest of the record may be written 
with a delay max. 100ms. The fast part is intended for fast changing values as e.g. currents, voltages or 
power. The parts are separated by a line in the record content list. 
 

 

 

1.  Values selection tree  
2.  Buttons for adding/removing values into/from the record structure  
3.  Buttons for ordering of the values in the record structure  
4.  Fast history separator. The fast part is located above the separator  
5.  Estimated number of records depending on record size  
6.  Record capacity usage indicator  

N

OTE

Values that are displayed in green color are recomended to be placed in the fast part. 
If  the  checkbox  Add  modules  to  history  automatically..  in  the  Modules  tab  is  checked  then  all  values  of  a 
module are automatically added into the history record when the module is inserted into the configuration. 

Time Stamp function 

The  controller  allows  user  to  define  when  the  history  records  are  written  even  though  there  is  no  other 
reason for history record (so called Time Stamp). 
It  is  possible  to  disable  time  stamping  function  (for  example  when  time  stamping  is  not  needed  and  just 
floods the history). It may be conditioned by activation of logical Binary Input function (T

IME

 

STAMP

 

ACT

) or it 

may be enabled always. 
Period of time stamping may be adjusted from 1 to 240 minutes. 

N

OTE

Beware of History flooding by to many Time Stamps (vital information may be overwritten). 

Summary of Contents for IG-NT GC

Page 1: ...l info comap control com www comap control com REFERENCE GUIDE Compact Controller for Stand by and Parallel Operating Gen sets Inteli New Technology Modular Gen set Controller Bank Controller IG NT GC...

Page 2: ...it breakers operation sequence CB fail detection 26 Remote Alarm Messaging 31 Controller Redundancy 32 Force value step by step guide 33 Values for continuous writing from external sources 35 General...

Page 3: ...ce Guide PDF 3 Modbus protocol 61 Value and setpoint codes 61 Technical data 61 Language support 61 Setpoint groups 64 Table of setpoints 64 Table of values 151 Table of binary input functions 183 Tab...

Page 4: ...zech Republic Phone 420 246 012 111 Fax 420 266 316 647 Web WWW COMAP CONTROL COM e mail info comap control com DOCUMENT HISTORY VERSION NUMBER RELATED SW VERSION DATE 1 1 2 0 31 3 2016 2 1 2 0 4 1 20...

Page 5: ...nt list of all Setpoints Values Logical Binary Inputs and Logical Binary Output IGS NT COX 3 1 0 Reference Guide pdf General description of COX applications for InteliGen NT and InteliSys NT Contains...

Page 6: ...START STOP or Disconnect output STARTER and outputs GCB CLOSE OPEN and MCB CLOSE OPEN The controller contains a large number of configurable setpoints because of this it is impossible to describe all...

Page 7: ...nary outputs Starter and Fuel to avoid unexpected automatic start of gen set and GCB closing Clarification of notation HINT This type of paragraph points out details to help user installation configur...

Page 8: ...ts a procedure adjustment etc which may cause damage or improper functioning of the equipment if not carried out correctly and may not be clear at first sight WARNING This type of paragraph indicates...

Page 9: ...eBox IS BC MINT 1 2 0 ant Gen set Controller firmware hardware archive compatibility The subordinated Gen set controller has to be loaded with appropriate FW IGS NT 3 3 0 and higher The special XXX MI...

Page 10: ...ion so that from the outside point of view the group behaves as one large gen set Bank controllers can be connected together so that large tree style multisites power stations can be created The aim o...

Page 11: ...set controllers can use address 1 31 See the Figure CAN bus wiring NOTE The gen set controller is never connected directly to the CAN A but it has to be always subordinated to some BankController NOT...

Page 12: ...er first starts the bank and when it is running the bank controller synchronizes the bank to the common bus This option is reccommended to be used whenever it is possible CAUTION Feeders and or mains...

Page 13: ...1 2 0 ComAp January 2019 IGS NT BC 1 2 0 Reference Guide PDF 13 Figure Power line wiring of system with the BCB Figure Power line wiring of system without the BCB GC Gen set controller IG NT IS NT BC...

Page 14: ...of wiring of the power lines see Power lines wiring paragraph above If BCB is used following AC values are to be measured Bank bus voltage 3phase required Common bus voltage 3phase required Bank curre...

Page 15: ...EXTENSION MODULES INTERC ONTR OLLER MONITORI NG DISPLAY L H L H IS NT LB 9 BANK CONTROLLER k L2 L3 L1 L2 L3 GENERATOR VOLTAGE MAINS VOLTAGE L1 L2 L3 TO OTHER GENSET BANKS COMMON BUSBAR BANK BUSBAR TO...

Page 16: ...T1A fuses for controller voltage measurement circuits protection BCB control and synchronizing If the system is equipped with BCB the BCB is controlled by the Bank controller There is a set of contro...

Page 17: ...mon bus as soon as all the available gensets in the bank are running If there is countervoltage on the common bus the breaker is synchronized otherwise it is closed to the dead bus In automatic mode t...

Page 18: ...oad and requested load reserve are started setpoint Powermanagement Pwr management is set as ENABLED The power management can be based on kW kVA or on relative reserve The start of the bank is a 1 sec...

Page 19: ...NT must be connected on the CAN2 to control gen set group kW I E Important setpoints ProcessControl SysLdCtrlPtM LDSHARING Import Export power factor Gen set group is controlled to keep constant or ad...

Page 20: ...ed gen set groups CAN segments to ensure the equal distribution of the load On the top of it it performs the inter bank powermanagement In the same time the second level of power management is perform...

Page 21: ...the banks and between the ge sets can be set differently Sum of available nominal power running gen sets in PM Total Load of the system Starting sequence Stopping sequence Bank 1 Priority 1 Bank 2 Pr...

Page 22: ...tion relevant to the actual load Thanks to the Automatic priority swapping function the Bank Controllers choose the banks to be running with consideration of their average running hours and the actual...

Page 23: ...BandContr2 PwrBandContr3 and PwrBandContr4 The load levels of the power bands are defined by sum of available nominal powers of banks that are adjusted to run in each particular power band and the loa...

Page 24: ...s have to work independently The group which the particular controller belongs to is adjusted by the setpoint Pwr management Control group If there is only one group in the site adjust the setpoint to...

Page 25: ...EM AUT mode b When MCB opens from parallel to mains operation in SEM AUT mode c Before MCB is opened in MAN mode by button The load shedding function is active in all controller modes except OFF Load...

Page 26: ...Load reconnection manual AutoLd recon DISABLED BO Load shed 2 Ld recon level Gen set power BO Load shed 3 BO Load shed 1 BI Man load recon opened opened opened no action Circuit breakers operation seq...

Page 27: ...CB UV coil output for undervoltage coil of the CB Permanently active 2s negative pulse 5s if synchronising is not provided by the particuilar CB is used for CB opening request CB status output indica...

Page 28: ...uld be issued after the second unsuccessfull attempt BO CB status 0 BI CB fdb neg 1 BI CB fdb 0 BO CB fail ON pulse has finished and CB status is not 1 CB fail is issued immediatelly 2s BO CB OFF coil...

Page 29: ...db BO CB close open BO CB UV coil During CB opening the CB status LBO is deactivated with change of the first feddback status Further behavior of UV output depends on the system status In case of tran...

Page 30: ...il BI CB fdb neg BI CB fdb BO CB close open BO CB UV coil BO CB status BO CB ON coil Closing pulse is shortened opening sequence is started immediatelly CB opening by protection or manual command butt...

Page 31: ...em An analog modem must be connected either to one of controller COM ports or to one of I LB modules connected to the controller via CAN2 bus The channel address must contain complete telephone number...

Page 32: ...possible to adjust number of attempts that controller performs in case of not successful Active Call Comms settings ActCallAttempt The language of messages can be changed Comms settings Acall SMS lan...

Page 33: ...nce the failed controller may not interpret it correctly VPIO VPI VPO CtrlHBeat FD Emerg manual CAN LOG BOUT LOG BIN Watched contr X Setpoint Emerg manual LOG BIN CAN BOUT BIN LOG BIN MAIN CONTROLLER...

Page 34: ...tc Select source setpoint or value For example if we add Force value Force value 1 to be forced to ProcessControl Export limit as value 0 DISABLED by Binary Input FORCEVALUEIN 1 we can change the func...

Page 35: ...o damage may occur External values are reverted back to their default initial value given by corresponding setpoint when Binary Input for their reset is active and they change to the previous value af...

Page 36: ...s repeated with adjusted period hh mm The timer duration is included in the preriod The mode of each timer channel is adjusted by an assigned setpoint The setpoints are located int the Timer settings...

Page 37: ...ucture 4 Fast history separator The fast part is located above the separator 5 Estimated number of records depending on record size 6 Record capacity usage indicator NOTE Values that are displayed in...

Page 38: ...tton is this function mapped to 0 first button 1 second button and so on Choose UserButton index and its function ON OFF etc Choose which colour will be available for this button Select which conditio...

Page 39: ...rtual Peripheral Inputs Outputs can be added to configuration and it will copy the state of Remote Switch on virtual output to its counterpart virtual input Refer to the figure below for example LBO R...

Page 40: ...es between all the controllers via CAN bus thus saving physical Inputs and Outputs and excess wiring Figure Adding of various modules SHBOUT 1 SHBIN 1 SHBOUT 2 Not Received Module SHBIN 2 is not inser...

Page 41: ...and are distributed among all controller in the system including all controllers connected to CAN A or CAN B like described by the Figure Virtual shared signals in the system with bank controller NOT...

Page 42: ...ller Up to 32 DISTBIN modules can be configured meaning that the controller will be receiving all DISTBOUT from all the controller even his own It is not possible to change the name of DISTBIN inputs...

Page 43: ...a CAN1 can be used For more information on how to use this module please refer to InteliGen InteliSys Communication Guide and to I CBEdit manual User MODBUS Users can define Modbus registers from 4287...

Page 44: ...ister port for writing Input value LBO ModbusSw16 ModbusSw1 ModbusSw1 46337 000F HEX 0000 0000 0000 1111 Register port for writing Input value LBO ModbusSw32 ModbusSw17 ModbusSw2 46338 F000 HEX 1111 0...

Page 45: ...sions in which values and some setpoints are interpreted or adjusted Power formats may be changed in Miscellaneous tab in GenConfig There are following Power Formats available 1 kW kVAr kVA kX V 0 1 k...

Page 46: ...Sys Start Stop Sys S S from IM2 BTB feedback Sys S S from IM1 M2 Start sheet output Sys S S from IM1 BTB feedback Sys S S from IM2 M1 Start sheet output Shared binary inputs Logical Group 2 Logical G...

Page 47: ...controllers support up to five Languages that is possible to switch during controller duty Every terminal i e Remote display or PC InteliMonitor can be switched to different language Use PC GenConfig...

Page 48: ...omAp January 2019 IGS NT BC 1 2 0 Reference Guide PDF 48 Frequency select 1500 1800 Preheat request Yes No Protection override Yes No Engine params Bin selector x Bin selector x CAN J1939 Force value...

Page 49: ...citation Loss 46 Current Unbalance 47 Voltage Assymetry 47 Phase Rotation 50 51 Overcurrent 50N 64 Earth Fault Current 51N 64 Earth Fault Current IDMT 55 Power Factor 59 Overvoltage 71 Gas Fuel Level...

Page 50: ...ks the internal signal Sys start stop to subordinated gen sets is deactivated The bank can t be started again while there is a Shutdown alarm in the Alarmlist Activates the output Common Sd as well as...

Page 51: ...ediate stop of the banks the internal signal Sys start stop to subordinated gen sets is deactivated The gen set can t be started again while there is a BOC alarm in the Alarmlist Activates the output...

Page 52: ...1 is not active The evaluation begins ForceBlockDel1 seconds after the input has been deactivated Force block 2 The alarms are beeing evaluated while the input Force block 2 is not active The evaluati...

Page 53: ...the engine because of them If the input is deactivated and some protections are still active or not yet reset the controller starts to take these protections into account and consequently stops the e...

Page 54: ...perating states Protections evaluation depends on the gen set state depends on the actual gen set conditions Configuration of User configurable protections in GenConfig It is possible to configure pro...

Page 55: ...figurable protection Open Protections tab in GenCofig and adjust parameters that are described below Existing custom protections list Add protection Delete protection Select the value for the protecti...

Page 56: ...hen they become inactive ENABLED Pressing of the fault reset button at any terminal or external button resets all alarms that are currently present in the alarm list Inactive alarms disappear from the...

Page 57: ...teliIO8 8 8 8 2 InteliIO16 0 16 0 2 I CB x x x x Configurable communication bridge IGL RA15 15 15 Green Red Yellow LED panel I AOUT8 8 8 Analog outputs VPIO 8 8 Virtual periphery I O module SHBIN 8 SH...

Page 58: ...onfiguration requires the highest password 7 level so only User 0 is able to modify the controller configuration or firmware Continuous internal evaluation of setpoints validity In case of detection o...

Page 59: ...IGS NT BC SW Version 1 2 0 ComAp January 2019 IGS NT BC 1 2 0 Reference Guide PDF 59 List of possible events The complete list is available in Troubleshooting guide...

Page 60: ...d free GND terminal is not connected 5 GND 2 RxD 3 TxD PC 5 GND 2 RxD 3 TxD RS232 RS232 230 VAC 0 VDC CONTROLLER Battery Required the same voltage potential between GND s RS 232 GenConfig functions Ex...

Page 61: ...cation speed The delay is not shorter than the time needed to send receive 3 and characters The complete description of Modbus communication protocol can be found in Modbus Protocol Reference Guide PI...

Page 62: ...lay from firmware version 1 5 supports following language code pages Code page Language Windows code 0 West European languages Windows 1252 134 Chinese GB 2312 162 Turkish Windows 1254 129 Korean Wind...

Page 63: ...IGS NT BC SW Version 1 2 0 ComAp January 2019 IGS NT BC 1 2 0 Reference Guide PDF 63 APPENDIX...

Page 64: ...s of all available setpoints values logical binary inputs and logical binary outputs that you can find in next chapters are common for standard gen set in MINT application and the Bank Controller For...

Page 65: ...0 99L 1 01 1 20 correspond to capacitive PF 0 99C 0 80C NOTE sign in the name of this setpoint marks that this setpoint is shared among all controllers connected by CAN2 bus Setpoint SysLdCtrl PtM Gr...

Page 66: ...adjusted by the logical functional analog input MLC AnExSysBld NOTE If the external source is selected the logical analog input must be configured at each gen set to the identical source The shared pe...

Page 67: ...point is used for adjusting the starting point of the Power derating 1 function where the gen set nominal power is still 100 of the setpoint Nomin power See the chapter Power derating for details NOTE...

Page 68: ...tarting point of the Power derating 2 function where the gen set nominal power is still 100 of the setpoint Nomin power See the chapter Power derating for details NOTE The setpoint actual physical dim...

Page 69: ...n NONE No synchronizing is enabled FORWARD GCB synchronizing is enabled REVERSE MCB synchronizing is enabled BOTH GCB and MCB synchronizing are enabled NOTE Although synchronizing of the particular br...

Page 70: ...ired for this function PRINCIPIAL SCHEME OF A SITE IF NEUTRAL CONT EACH The COMMON option should be used if there is one common neutral contactor for the whole site The outputs Neutral CB C O from all...

Page 71: ...roller to specify the address of the related main controller in CAN based rendundant systems Adjust this setpoint to 0 if the controller is not used as redundant or if wired rendundancy system is used...

Page 72: ...T ratio sec Group Basic settings Range units 5A 1A Related FW 3 0 Description Nominal current of the secondary side of the generator current transformers The primary side is adjusted by setpoint CT ra...

Page 73: ...st the generator voltage transformers ratio NOTE Adjust the setpoint to the value of 1 0 if the generator voltage is connected directly to the controller terminals i e without transformers NOTE Exampl...

Page 74: ...asurement The range 120V is intended for high voltage applications where voltage transformers with 100V secondary range are used or for alternative American 120V measurement Setpoint Vb InpRangeSel Gr...

Page 75: ...int is used to adjust the nominal rated generator voltage phase to phase This setpoint is also recalculated automatically when the phase neutral nominal voltage BankNomV is changed This setpoint can b...

Page 76: ...MP 97 hence the desired values are reached Setpoint BusNomVph ph Group Basic settings Range units 17 60000 V Related FW 3 0 Description In application MINT and COX This setpoint is used to adjust the...

Page 77: ...s nominal phase phase voltage is 400V measured voltages are L12 400V L23 390V L31 390V the L23 and L31 are at 97 5 of the nominal It is obvious that if the situation is evaluated from phase neutral vo...

Page 78: ...set is started and stopped only manually using START and STOP buttons or external buttons wired to appropiate binary inputs however the the full start sequence up to the moment when the engine is load...

Page 79: ...XTBUTTONS BOTH Related FW 3 0 Description The setpoint selects which set of control buttons is currently active Its function depends on which type of controller is used Please refer to the section whi...

Page 80: ...n orange box depends on functions assigned to each button individually If any function in the list in the note below is assigned to these buttons then it behaves as buttons in the red box if any other...

Page 81: ...s as buttons in the green box The binary inputs for external buttons are affected in the same way as in the case of IGS NT built in monochrome display by this setpoint NOTE In the case that more IV di...

Page 82: ...e of increasing of the PulseCounter 1 module The module counts pulses at the input PulseCounter 1 and if the input pulses counter reaches value given by this setpoint the counter value PulseCounter 1...

Page 83: ...group Statistic is increased by 1 and input pulses counter is reset to 0 Both counter value and input pulses counter are stored in the nonvolatile memory Group Comms settings Setpoint Gen set name Gr...

Page 84: ...er Communication DIRECT Connection to a local PC via RS232 or RS485 with internal or external converter interface Use this option also for IG IB connected via RS232 cable The internal RS485 converter...

Page 85: ...EM HW Modem point to point connection to a remote PC with hardware data flow control using signals RTS CTS Full modem cable is required for this option MODEM SW Modem point to point connection to a re...

Page 86: ...CSpd Group Comms settings Range units 9600 19200 38400 57600 bps Related FW 3 0 Description The setpoint adjusts the communication speed on the COM2 connector when it is switched to MODBUS or MODBUS M...

Page 87: ...ated FW 3 0 Description This setpoint can be used to add extra AT commands at the end of the initialization sequence of the modem connected to the COM2 port The command can be entered with as well as...

Page 88: ...rollers CAN bus length limited up to 900 meters Change of this setpoint is applied after the controller is switched off and on again NOTE Use low speed for long distance connection only Set all connec...

Page 89: ...al is disconnected automatically after 5 min of inactivity and next communication request from the same terminal is considered as a new connection When logging is enabled in certain conditions the his...

Page 90: ...usted FIXED The ethernet connection is adjusted fixedly according to the setpoints IP address Net mask Gateway IP DNS IP This method should be used for classic ethernet or Internet connection When thi...

Page 91: ...is setpoint is used to adjust the IP address of the gateway of the network segment where the controller is connected In Automatic settings mode this setpoint is used to display the gateway IP address...

Page 92: ...a connection to the Internet The AirGate server address is adjusted by the setpoint AirGate addr Setpoint AirGate IP Group Comms settings Range units max 32 characters Related FW 3 0 Description This...

Page 93: ...39 109 of the SMTP server Please ask your internet provider or IT manager for this information NOTE You may also use one of free SMTP servers e g smtp gmail com However please note that some free SMTP...

Page 94: ...Range units Related FW 3 0 Description In fixed settings mode this setpoint is used to adjust the domain name server DNS which is needed to traslate domain names in e mail addresses and server names...

Page 95: ...tie breakers position Normally a collision would be indicated if there were more sources on the bus and this setpoint can be used to disable the evaluation of collisions in this special case Group Co...

Page 96: ...t is adjusted to OFF the horn output is not activated at all the NO TIMEOUT position means the horn output is not deactivated until the alarms are reset Setpoint BinInp delay 1 Group Engine protect Ra...

Page 97: ...uts can have either fixed 0 5s evaluation delay or there are three independent delay setpoints and one of them can be assigned to each particular binary input protection Setpoint ForceBlockDel1 Group...

Page 98: ...NABLED Pressing of the fault reset button at any terminal or external button resets all alarms that are currently present in the alarm list Inactive alarms disappear from the alarm list immediately ac...

Page 99: ...e after the gen set is synchronized to the mains i e the Warming load can be adjusted also below the sepoint Min Power PtM This setpoint is also used as the requested load level if a protection of Low...

Page 100: ...od of the generator voltage The period is either 0 02s for 50Hz systems or 0 0166s for 60Hz systems E g if the delay is set to 0 03s at 50Hz system the real delay will be 0 04s Setpoint 2Inom del Grou...

Page 101: ...ion which is adjusted by setpoint Bank V Sd NOTE The BOC protections are active after the Max stab time elapsed or after the GCB was closed then while the GCB is closed and then also during cooling if...

Page 102: ...tended to be used as first level protection with lower threshold whereas the shutdown one is intended as second level with higher threshold Setpoint Bank V del Group Bank protect Range units 0 00 600...

Page 103: ...tection activates if the frequency in phase L3 drops below the threshold for time longer than Bank f del NOTE The generator underfrequency protection is Breaker open and cool down BOC type NOTE The BO...

Page 104: ...0 s Related FW 3 0 Description The setpoint adjusts the delay for generator reverse power protection The threshold for the protection is adjusted by setpoint Reverse power Setpoint Nom EthFltCurr Gro...

Page 105: ...ernal counter accumulates and it starts continuously decreasing when the EarthFault Current goes below Nom EthFltCurr This function prevents the protection from completely reseting when the EarthFault...

Page 106: ...sm of universal analog protections That means this setpoint is one of general purpose setpoints which may be used for different purpose if the protection is deleted from the configuration Setpoint Ban...

Page 107: ...iversal analog protection at the value Bus V unbal which is calculated as maximum difference between two bus phase voltages The protection activates if the voltage unbalance gets over the threshold fo...

Page 108: ...wer management mode ABS KW The power management is based on actual active power and gen set nominal power The reserves are calculated and adjusted in kW ABS KVA The power management is based on actual...

Page 109: ...please use IGS NT PSC firmware in additional controller more information about this FW can be found on our webpages www comap cz Note that this priority swapping function may be used only if Pwr mgmt...

Page 110: ...master role Setpoint SysAMFstrtDel Group Pwr management Range units 0 600 s Related FW 3 0 Description This setpoint adjusts the delay between closing of the input Sys start stop and activation of th...

Page 111: ...me situations to allow genset start after Sys Start Stop gets active It is not destined for normal operation Please refer to the Troubleshooting guide for more information chapter MGCB is not closed a...

Page 112: ...dResStop 2 Group Pwr Management Range units LoadResStrt 2 32000 kX Related FW 3 0 Description This setpoint is used to adjust the load reserve for stop in absolute mode i e Pwr mgmt mode ABS kW or ABS...

Page 113: ...nputs is active the set 1 is selected NOTE The reserve for stop must be always adjusted higher than the reserve for start Setpoint LoadResStrt 4 Group Pwr Management Range units 32000 LoadResStop 4 kX...

Page 114: ...Strt 1 Group Pwr Management Range units 0 LdResStop 1 Related FW 3 0 Description This setpoint is used to adjust the load reserve for start in relative mode i e Pwr mgmt mode REL if the reserve set 1...

Page 115: ...in the chapter Reserves minimal running power The currently active reserve set is selected by binary inputs Load res 2 Load res 3 and Load res 4 If none of these inputs is active the set 1 is selecte...

Page 116: ...binary inputs Load res 2 Load res 3 and Load res 4 If none of these inputs is active the set 1 is selected Setpoint LdResStop 4 Group Pwr Management Range units LdResStrt 4 110 Related FW 3 0 Descript...

Page 117: ...speed up the start up of the next gen set NOTE The setpoint takes place only in island operation Setpoint NextStopDel Group Pwr Management Range units 0 3600 s Related FW 3 0 Description This setpoint...

Page 118: ...are 3 different MinRunPower setpoints this particular one is activated by the input MinRun power 2 NOTE If more than one binary input for MinRunPower activation is closed MinRunPower with higher numbe...

Page 119: ...be created so that the total nominal power of the Power band 1 2 3 4 Setpoint PwrBandContr 2 Group Pwr management Range units 1 2 1 2 3 1 3 2 3 1 2 3 Related FW 3 0 Description This setpoint is used t...

Page 120: ...0 Description This setpoint is used for adjusting the delay of changing the power band if the load demand rose above the upper limit of the current power band Learn more about this topis in the chapte...

Page 121: ...cated at the right side of the group link breaker bus tie breaker If this particular controller is not used for the group link function adjust this setpoint to 1 COMMON Group Sync Load ctrl Setpoint V...

Page 122: ...oup Sync Load Ctrl Range units 0 90 Related FW 3 0 Force value possible YES Description This setpoint adjusts maximum absolute value of difference between actual phase angle between the generator and...

Page 123: ...neral information about regulation loops and their adjustment Setpoint Freq int Group Sync Load Ctrl Range units 0 100 Related FW 3 0 Description This setpoint adjusts the relative integration factor...

Page 124: ...amp is adjusted by the setpoint Load ramp in subordinated gen sets Setpoint BCB open del Group Sync Load Ctrl Range units 0 1800 s Related FW 3 0 Force value possible YES Description This setpoint adj...

Page 125: ...eral information about regulation loops and their adjustment Setpoint Voltage Int Group Volt PF Ctrl Range units 0 100 Related FW 3 0 Description This setpoint adjusts the relative integration factor...

Page 126: ...een the default names of the force value function blocks associated binary inputs and the default names of the reserved setpoints In other words the setpoint with default name Force value 3 is not rel...

Page 127: ...Group Force value Range units Related FW 3 0 Description This is one of the 16 setpoints reserved for using as alternative setpoints for the force value functions The alternative setpoint is to be ass...

Page 128: ...n and renamed in GenConfig See also the input Force value 1 NOTE It is not obligatory to use one of these reserved setpoints for a force value function It is possible to use also any other setpoint or...

Page 129: ...on NOTE There isn t any relation between the default names of the force value function blocks associated binary inputs and the default names of the reserved setpoints In other words the setpoint with...

Page 130: ...ue 3 function block Setpoint Force value 12 Group Force value Range units Related FW 3 0 Description This is one of the 16 setpoints reserved for using as alternative setpoints for the force value fun...

Page 131: ...icular force value function and renamed in GenConfig See also the input Force value 1 NOTE It is not obligatory to use one of these reserved setpoints for a force value function It is possible to use...

Page 132: ...not obligatory to use one of these reserved setpoints for a force value function It is possible to use also any other setpoint or value with matching dimension and decimal resolution NOTE There isn t...

Page 133: ...ption This setpoint adjusts the high limit of the value of ExtValue 1 if the value is lowered raised by the binary inputs ExtValue1 up and ExtValue1 down The ExtValue 1 is never raised over this limit...

Page 134: ...is never lowered below this limit NOTE This limit is not taken into account if the value ExtValue 2 is written remotely from a terminal using the appropriate command ExtValue n NOTE For IS NT only Se...

Page 135: ...HiLim X Related FW 3 0 Description This setpoint adjusts the low limit of the value of ExtValue 3 if the value is lowered raised by the binary inputs ExtValue3 up and ExtValue3 down The ExtValue 3 is...

Page 136: ...possible YES Description This setpoint adjusts the reset initial value of the ExtValue 4 This initial value is applied either when the controller is powered on or when the ExtValue 4 is reset by the b...

Page 137: ...d FW 3 0 Force value possible YES Force value possible YES Description This setpoint adjusts the rate pre second at which the ExtValue 4 is beeing changed while the input ExtValue4 up or ExtValue4 dow...

Page 138: ...level in of nominal power of gen set for load shedding When the relative load level exceeds this level for more than Ld shed delay time the next load shedding output is closed NOTE Learn more about l...

Page 139: ...just time period the relative load level must be below the Ld recon level limit to allow reconnection of next load group NOTE Learn more about load shedding in the separate chapter Load shedding Setpo...

Page 140: ...l 3 Group Timer settings Range units Related FW 3 0 Description This setpoint adjusts the mode of the Timer channel 3 Output from this channel is available in the combined output TimerAct 1 4 NOTE See...

Page 141: ...l 7 Group Timer settings Range units Related FW 3 0 Description This setpoint adjusts the mode of the Timer channel 7 Output from this channel is available in the combined output TimerAct 5 8 NOTE See...

Page 142: ...11 Group Timer settings Range units Related FW 3 0 Description This setpoint adjusts the mode of the Timer channel 11 Output from this channel is available in the combined output TimerAct 9 12 NOTE Se...

Page 143: ...imers Setpoint Timer channel 15 Group Timer settings Range units Related FW 3 0 Description This setpoint adjusts the mode of the Timer channel 15 Output from this channel is available in the combined...

Page 144: ...ts DISABLED ENABLED Related FW 3 0 Force value possible YES Force value possible YES Description This setpoint is used to enable sending SMS and or e mail alerts when a protection configured as Alarm...

Page 145: ...point is used to enable sending SMS and or e mail alerts when a BrkOpen CoolDn type alarm occurs See the chapter Alarm management for more information about protection types Setpoint Mains protect Gro...

Page 146: ...calls SMS Range units DISABLED ENABLED Related FW 3 0 Force value possible YES Description This setpoint is used to enable sending SMS and or e mail alerts when a Sd Override type alarm occurs See th...

Page 147: ...he selected alert type e g it must contain e mail address if the alert type is e mail See the chapter Alarm messaging for more details Setpoint AcallCH3 Type Group Act calls SMS Range units Related FW...

Page 148: ...e details Setpoint AcallCH5 Type Group Act calls SMS Range units Related FW 3 0 Description The setpoint is used to specify the alert type of the active calls channel 5 See the chapter Alarm messaging...

Page 149: ...ll SMS lang Group Act calls SMS Range units 1 7 Related FW 3 0 Description The setpoint specifies in which language the active SMS and e mail messages are issued Adjust the setpoint to the index of th...

Page 150: ...bled the current season is summer and the controller is located in the northern hemisphere WINTER S The automatic change is enabled the current season is winter and the controller is located in the so...

Page 151: ...has lowest address If date time is changed at one controller it is automatically updated also in all other controllers in the group NOTE Setpoint with the symbol are synchronized between controllers T...

Page 152: ...erator active power in phase L2 Value Act pwr L3 Group Bank values Units kW Related FW 3 0 Description Generator active power in phase L3 Value React power Group Bank values Units kVAr Related FW 3 0...

Page 153: ...kVA Related FW 3 0 Description Generator apparent power in phase L1 Value Appar pwr L2 Group Bank values Units kVA Related FW 3 0 Description Generator apparent power in phase L2 Value Appar pwr L3 Gr...

Page 154: ...rator load L means inductive load C is capacitive and R is resistive load power factor 1 Value Pwr factor L1 Group Bank values Units Related FW 3 0 Description Generator power factor in phase L1 Value...

Page 155: ...harmonic waveforms because a simplified method can be used for calculation of it s value However if this simplified method is used for significantly distorted waveforms it may provide inaccurate resu...

Page 156: ...and the displayed voltage is adjusted by the setpoint VT ratio Value Bank V L3 N Group Bank values Units V Related FW 3 0 Description Bank voltage in phase L3 NOTE The ratio between the voltage measu...

Page 157: ...V Related FW 3 0 Description Bank voltage between phases L3 and L1 NOTE The ratio between the voltage measured at the input terminals and the displayed voltage is adjusted by the setpoint VT ratio Va...

Page 158: ...voltages at one moment and expressed in of the nominal voltage NOTE This value can be used for creating the generator voltage unbalance protection using the universal analog protections Value Bank I...

Page 159: ...io between the voltage measured at the input terminals and the displayed voltage is adjusted by the setpoint Vm VT ratio Value Bus V L2 N Group Bus values Units V Related FW 3 0 Description Bus voltag...

Page 160: ...lue Bus V L3 L1 Group Bus values Units V Related FW 3 0 Description Bus voltage phase L3 to L1 Value Bus V unbal Group Bus values Units V Related FW 3 0 Description Bus voltage unbalance The value is...

Page 161: ...value function If the Gen set size optimalization is active then the actual priority is given by the optimalization function Value Act Reserve Group Pwr management Units Related FW 3 0 Description Act...

Page 162: ...opped This value contains the following Nominal power of gen set which is next to be stopped LdResStp 100 Sum of nominal powers of gen sets loaded in power management except the one which is next to b...

Page 163: ...the value Engine state Value TotRunPact Q Group Sync Load ctrl Units kVAr Related FW 3 0 Description Sum of reactive power of all banks within the group that are connected to the bus Value TotRunPact...

Page 164: ...ts of this value show 1 if the bank controller receives messages from the subordinated gen set controller which has address corresponding with the bit position Bit 0 represents address 1 etc This valu...

Page 165: ...7 32 NOTE The bit which corresponds to the own controller is always set to 1 Value YEL16 Group Gensets Units Related FW 3 0 Description Bits of this value show 1 if the bank controller receives the Ye...

Page 166: ...Force value Units Related FW 3 0 Description This data object is intended for remote control of the gen set via the communication if some kind of data is to be passed into the controller This object...

Page 167: ...bject See an example at the object ExtValue1 Value ExtValue3 Group Force value Units Related FW 3 0 Description This data object is intended for remote control of the gen set via the communication if...

Page 168: ...ls Value CPU Temp Group Analog CU Units C Related FW 3 0 Description Temperature inside the controller on the CPU Value D Group Analog CU Units V Related FW 3 0 Description Voltage measured at the D t...

Page 169: ...level measurement Value AIN CU 4 Group Analog CU Units configurable Related FW 3 0 Description This is the value of the analog input 4 of the controller Analog inputs are fully configurable so the nam...

Page 170: ...is a bit array containing status of logical binary outputs 1 16 of the controller Bit0 represents LBO1 bit1 represents LBO2 etc NOTE All terminals display binary values in human readable form from lef...

Page 171: ...Related FW 3 0 Description This is a bit array containing status of logical binary outputs 49 64 of the controller Bit0 represents LBO49 bit1 represents LBO50 etc NOTE All terminals display binary val...

Page 172: ...values Value LogBout 7 Group Log bout Units Related FW 3 0 Description This is a bit array containing status of logical binary outputs 97 112 of the controller Bit0 represents LBO97 bit1 represents L...

Page 173: ...ary values are displayed from right to left Value RemoteControl Group Log bout Units Related FW 3 0 Description This is a bit array containing status of the binary outputs Remote control1 Remote contr...

Page 174: ...our distributor if you need to retrieve your password Value CAN16 Group Info Units Related FW 3 0 Description Bits of this value show 1 if the bank controller receives messages from the another bank c...

Page 175: ...s active role in the power management Bit 0 represents address 17 etc This value contains information about controllers with addresses 17 32 Value GL16 Group Info Units Related FW 3 0 Description Bits...

Page 176: ...t state of the breaker control The text representation of each code can be obtained by the procedure described at the value Engine state Value Timer text Group Info Units Related FW 3 0 Description Co...

Page 177: ...le in the value NextTime1 4 NOTE More information about timers is available in the chapter General purpose timers Value NextTime5 8 Group Info Units Related FW 3 0 Description This value contains time...

Page 178: ...the value NextTime9 12 NOTE More information about timers is available in the chapter General purpose timers Value NextTime13 16 Group Info Units Related FW 3 0 Description This value contains time o...

Page 179: ...gistration denied 3 Can not register no free capacity in the server 4 Can not register other reason 5 Connected registered authorized Value Latitude Group Info Units Related FW 3 0 Description This va...

Page 180: ...p Statistics Units h Related FW 3 0 Description Engine operation hours counter If an ECU is configured and it provides engine hours value the value is taken from ECU If the value is not available from...

Page 181: ...alarm WrnServiceTime is issued as soon as the timer counts down to zero Value Service time 2 Group Statistics Units h Related FW 3 0 Description This is maintenance countdown timer 2 The timer is loc...

Page 182: ...ription This counter counts while the controller is in not ready state i e it can not be started The reason of the not ready state may be either some 2nd level alarm or the controller switched in OFF...

Page 183: ...ted FW 3 0 Description This is the value of PulseCounter 4 module See the binary input PulseCounter 4 NOTE Available in IS NT only Table of binary input functions Binary input BCB feedback Related FW...

Page 184: ...wr Management setpoint the gen set excluded from the power management and starts and stops only according to position of this input If the input is not active the gen set is always stopped in AUT mode...

Page 185: ...gramming is allowed in OFF mode only and GenConfig is not able to switch the controller to OFF mode while MAN mode is forced by this input Binary input REMOTE Remote AUT Related FW 3 0 Description The...

Page 186: ...aves the gen set in operation If there are any protections still active or not reset in the moment when the input is deactivated the controller will react to them in a standard way Following protectio...

Page 187: ...e controller has no power supply before the gen set is started It may be also useful in case of testing the gen set or in case of a failure which does not allow the gen set to be controlled by the con...

Page 188: ...re Starting Idle run Running ForwardSynchro ReverseSynchro Warming Soft load Loaded Soft unld Cooling Stopping Crancking PeakShaveAct Binary input ManualLdRecon Related FW 3 0 Description This input i...

Page 189: ...rd The function of the input is identical as function of the stop button on the controller front panel The input is enabled only if the setpoint Local Button is set to position EXTBUTTONS or BOTH Bina...

Page 190: ...wer management is switched to absolute mode LdResStrt 2 and LdResStop 2 if the power management is switched to relative mode CAUTION All controllers cooperating together in Power management must have...

Page 191: ...s used to activate the load reserve set 4 instead of the set 1 which is active by default The set 4 is adjusted by setpoints LoadResStrt 4 and LoadResStop 4 if the power management is switched to abso...

Page 192: ...UTION All controllers cooperating together in Power management must have the same minimal running power selected NOTE It is possible to use virtual peripheries for distribution of the binary signal fr...

Page 193: ...e setpoint Priority ENCODING TABLE PRIORITY INPUT A INPUT B INPUT C INPUT D Default 0 0 0 0 1 1 0 0 0 2 0 1 0 0 3 1 1 0 0 4 0 0 1 0 5 1 0 1 0 6 0 1 1 0 7 1 1 1 0 8 0 0 0 1 9 1 0 0 1 10 0 1 0 1 11 1 1...

Page 194: ...ty NOTE See encoding table in the description of the input Priority sw A Binary input GroupLink Related FW 3 0 Description This input is used for logical connection and disconnection of the two gen se...

Page 195: ...input pulses counter are stored in the nonvolatile memory The PulseCounter modules are intended e g for connecting external energy or fuel meters with pulse outputs NOTE Minimal pulse width as well as...

Page 196: ...al energy or fuel meters with pulse outputs NOTE Minimal pulse width as well as minimal pause between two succesive pulses is 100ms NOTE The counter value can be reset in the InteliMonitor statistics...

Page 197: ...details about timers Binary input Timer block 5 Related FW 3 0 Description This input is used to disable temporarily the output from the Timer channel 5 NOTE See also the setpoint TimerChannel 5 and o...

Page 198: ...rily the output from the Timer channel 9 NOTE See also the setpoint TimerChannel 9 and output TimerAct 9 12 NOTE See the chapter Timers for more details about timers Binary input Timer block 10 Relate...

Page 199: ...TimerAct 13 16 NOTE See the chapter Timers for more details about timers Binary input Timer block 14 Related FW 3 0 Description This input is used to disable temporarily the output from the Timer chan...

Page 200: ...is input is active the value of ExtValue 1 is contiously beeing decreased at the rate of ExtValue1 rate until it reaches ExtValue1LoLim NOTE If this input is used configured the ExtValue 1 can t be wr...

Page 201: ...ng decreased at the rate of ExtValue3 rate until it reaches ExtValue3LoLim NOTE If this input is used configured the ExtValue 3 can t be written remotely from a remote terminal using the command ExtVa...

Page 202: ...reset to it s default value when this input is activated and held there until the input is deactivated The default value is given by the setpoint ExtValue2deflt While the reset input is active The va...

Page 203: ...er to issue an active call e mail SMS via the channel 1 Type of the channel is to be adjusted by the setpoint AcallCH1 Type This input can be used to inform a remote user about a specific non alarm si...

Page 204: ...lock to the binary signal mentioned above and select protection type AL indication 3 Configure the binary signal mentioned above onto the logical binary input IssueActCallC3 Binary input IssueActCallC...

Page 205: ...Local display means that it is connected to dedicated RS485 There is possibility to connect up to 2 external displays in IG NT BB or 1 in IG NT It is possible to connect up to 3 external displays in...

Page 206: ...itself In such case the controller would issue an Underspeed alarm Connecting this input to an appropriate ECU output which provides information that the engine has been stopped by the ECU prevents t...

Page 207: ...rriden by value of the alternative setpoint assigned to the Force value 1 block NOTE If there are more than one force value blocks configured onto one setpoint then the highest priority has the block...

Page 208: ...isplayed in GenConfig in the Force value window at the related setpoint NOTE Watch a training video about force value function here http www comap cz support training training videos NOTE See an examp...

Page 209: ...re http www comap cz support training training videos NOTE See an example in the description of the binary input Force value 1 Binary input ForceValueIn 5 Related FW 3 0 Description This input activat...

Page 210: ...ocks configured onto one setpoint then the highest priority has the block with the lowest index i e the first active block according to the list displayed in GenConfig in the Force value window at the...

Page 211: ...value of the setpoint to which the Force value 10 block is configured will be overriden by value of the alternative setpoint assigned to the Force value 10 block NOTE If there are more than one force...

Page 212: ...value window at the related setpoint NOTE Watch a training video about force value function here http www comap cz support training training videos NOTE See an example in the description of the binar...

Page 213: ...iden by value of the alternative setpoint assigned to the Force value 15 block NOTE If there are more than one force value blocks configured onto one setpoint then the highest priority has the block w...

Page 214: ...ed Binary input Force block 3 Related FW 3 0 Description This is one of three binary inputs used for user defined blocking of protections If the input is active all the protections that have Protectio...

Page 215: ...ription This is one of three binary inputs Lang sel int A Lang sel int B Lang sel int C used for selecting language of the built in IG NT terminal display As the IS NT does not have built in terminal...

Page 216: ...sed to be directly attached to the controller or mounted close to it NOTE Using these inputs for language selection is an option only If the inputs are not configured the language can be selected usin...

Page 217: ...lects the default language of the terminal i e the language which is adjusted in the terminal using it s menus NOTE The reaction on changes of these inputs is delayed about 1 sec to ensure the new com...

Page 218: ...es the reinitialization of the display Function of the controller is not influenced Binary input Lang sel D 2 C Related FW 3 0 Description This is one of three binary inputs Lang sel D 2 A Lang sel D...

Page 219: ...nal 3 The terminal 3 is available in IS NT only NOTE Using these inputs for language selection is an option only If the inputs are not configured the language can be selected using the menus on the te...

Page 220: ...onfigured NOTE Language index 0 selects the default language of the terminal i e the language which is adjusted in the terminal using it s menus NOTE The reaction on changes of these inputs is delayed...

Page 221: ...lows user to activate chosen function in ScreenEditor tool for GenConfig for particular screen instrument User may choose from the following functions NONE SHOW HIDE No action regarding this screen in...

Page 222: ...om condition for this swapping function Binary input User mask 3 Related FW 3 0 Description This input allows user to activate chosen function in ScreenEditor tool for GenConfig for particular screen...

Page 223: ...input is used to adjust the backlight intensity of the IG NT built in terminal display by an analog input e g a potentiometer If this input is configured to a physical analog input or other value the...

Page 224: ...rminal board between a thermocouple and the IS AIN8 module and there is a significant temperature difference between this terminal board and the module it is necessary to measure the temperature at th...

Page 225: ...l temperature of the module This analog input is intended for measuement of this thermocouple compensation temperature for the IS AIN8 module with index 4 NOTE Thermocouples without internal compensat...

Page 226: ...s together with the output Alarm It opens when the output Alarm is opened or Horn reset button is pressed or Horn timeout has elapsed Binary output CommonAlLev 1 Related FW 3 0 Description This output...

Page 227: ...e end of the Starting period and opens at the end of the Aftercooling period which takes place after the engine has been fully stopped Duration of the aftercooling period is adjusted by the setpoint A...

Page 228: ...extended to 5sec See timing diagram of all available breaker control outputs in the description of the BCB close open output There are also other outputs availabe for BCB control BCB close open BCB O...

Page 229: ...scription The output is closed while the actual reserve is above the selected reserve for start Binary output Syst res 1 OK Related FW 3 0 Description The output is closed while the actual reserve is...

Page 230: ...Related FW 3 0 Description The output is closed while the generator over under voltage alarm is present in the alarm list Binary output Vbus Related FW 3 0 Description The output is closed while the...

Page 231: ...while there is at least one alarm of the Slow stop type present in the alarm list The alarm can be in any state i e active unconfirmed active confirmed or inactive unconfirmed See the chapter Alarm ma...

Page 232: ...ted FW 3 0 Description The output is closed for 1s when any alarm of History record type appears See the chapter Alarm management for more information Binary output CommonActLev 1 Related FW 3 0 Descr...

Page 233: ...activated Binary output HrnResButnEcho Related FW 3 0 Description This output provides 1s pulse when Horn reset button is pressed on the controller front panel or Horn reset button is pressed on any...

Page 234: ...o on the BCB fdb neg input If only the positive feedback input is used the output mirrors the feedback If both feedbacks are used and they match each other the output indicates the BCB position accord...

Page 235: ...0 Description This output generates 100ms pulse always when the internal kWh counter incremented Binary output In synchronism Related FW 3 0 Description This output is closed during synchronization w...

Page 236: ...output Neutral CB C O Related FW 3 0 Description This output is intended for control of the neutral contactor The output provides continuous signal while the neutral contactor has to be closed Use th...

Page 237: ...redundant controller has not received two consequent messages from the main controller The address of the main controller for the particular redundant one is selected by the the setpoint Watched Contr...

Page 238: ...ne of the channels is active NOTE See the chapter Timers for more details about timers Binary output TimerAct 5 8 Related FW 3 0 Description This is combined output from timer channels 5 8 The output...

Page 239: ...only indicates whether the system is able to fulfil it or not Binary output Ready for Load Related FW 3 0 Description This output is closed while the gen set is running it s voltage and frequency are...

Page 240: ...the prestart phase and remains closed during prestart cranking and starting phases The output is opened either when the bank goes to running phase or when it failed to start See the diagram in the de...

Page 241: ...lector 1 Related FW 3 0 Description Output is closed or opened according to the setpoint Bin selector 1 NOTE The output is intended for ECU controlled engines to switch on off some particular ECU func...

Page 242: ...te depends on function assigned to the related button It is possible to lock UserButton commands in configuration to specific user level Buttons 1 8 and 9 16 are locked separately ON Pressing the butt...

Page 243: ...puls of length of one second to be generated from the moment of button pushing Binary output User Button 3 Related FW 3 0 Description This output can be specified for example on buttons on IV 5 8 or i...

Page 244: ...Repeated pressing of button during the closed period one second causes issuing another puls of length of one second to be generated from the moment of button pushing Binary output User Button 5 Relat...

Page 245: ...t is changed to the opposite state PULSE ON Pressing the button issues log binary output User Button X to close for one second NOTE Repeated pressing of button during the closed period one second caus...

Page 246: ...ned When the output is opened and the button is pressed state is not changed ON OFF Pressing the button changes the state of log binary output User Button X to opened or closed depending on previous s...

Page 247: ...ON Pressing the button changes the state of log binary output User Button X to closed When the output is closed and the button is pressed state is not changed OFF Pressing the button changes the state...

Page 248: ...agram in InteliMonitor Its state depends on function assigned to the related button It is possible to lock UserButton commands in configuration to specific user level Buttons 1 8 and 9 16 are locked s...

Page 249: ...ated from the moment of button pushing Binary output User Button 14 Related FW 3 0 Description This output can be specified for example on buttons on IV 5 8 or in SCADA diagram in InteliMonitor Its st...

Page 250: ...Repeated pressing of button during the closed period one second causes issuing another puls of length of one second to be generated from the moment of button pushing Binary output User Button 16 Rela...

Page 251: ...ails about how to control the output from InteliMonitor and the Modbus chapter in the latest communication guide for information about control the output using Modbus Binary output RemoteControl3 Rela...

Page 252: ...l the output from InteliMonitor and the Modbus chapter in the latest communication guide for information about control the output using Modbus Binary output RemoteControl7 Related FW 3 0 Description T...

Page 253: ...s enabled and there is not any dongle with PMS feature inserted in the controller The controller is in situation when the load sharing should beeing performed however there is not any dongle with LS f...

Page 254: ...Sd Stop fail alarm is present in the alarm list This alarm appears when the gen set indicates that it is rotating although it has to be stopped This situation can occur when the gen set starts to rot...

Page 255: ...ad condition Alarm output Stp GCB fail Related FW 3 0 Description This output is closed while the GCB fail alarm is present in the alarm list Alarm output BOC NCB fail Related FW 3 0 Description This...

Page 256: ...gen set state running stopped and position of the input Oil press Alarm output OfL StartBlck Related FW 3 0 Description This output is closed while message OfL StartBlck is present in the alarm list...

Page 257: ...ged in GenConfig Alarm output PLC State 3 Related FW 3 0 Description The output is closed while the alarm generated by the PLC block Force prot 3 is present in the alarm list NOTE The actual text whic...

Page 258: ...essage number Alarm output UnivState 3 Related FW 3 0 Description The output is closed while the alarm generated by the Universal analog protection where the Message 3 is used is present in the alarm...

Page 259: ...message number Alarm output UnivState 8 Related FW 3 0 Description The output is closed while the alarm generated by the Universal analog protection where the Message 8 is used is present in the alar...

Page 260: ...enerated by the Universal analog protection where the Message 13 is used is present in the alarm list See the UnivState 1 for picture how to find the message number Alarm output UnivState 14 Related F...

Reviews: