IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
52
12.5% of the
sensor
range (25
Ω)
Sensor fail limit would be
-15
Ω what is physically
imposible so sensor fail is
not detected even for 0 ohm
First point of
the curve
100% of the sensor range
Last point of
the curve
Sensor fail
limit
Se
ns
or
fai
l a
rea
10
11,25
Bar
10
210
235
Ω
12.5% of the
sensor
range (25
Ω)
-15
H
INT
The sensor fail alarm does not influence the gen-set operation
Blocking types
B
LOCKING
TYPE
D
ESCRIPTION
All the
time
The alarms are beeing evaluated all the time the controller is switched on.
Force
block 1
The alarms are beeing evaluated while the input
Force block 1
is not active. The
evaluation begins
ForceBlockDel1
seconds after the input has been deactivated.
Force
block 2
The alarms are beeing evaluated while the input
Force block 2
is not active. The
evaluation begins
ForceBlockDel2
seconds after the input has been deactivated.
Force
block 3
The alarms are beeing evaluated while the input
Force block 3
is not active. The
evaluation begins
ForceBlockDel3
seconds after the input has been deactivated.
El. prot
The alarms are beeing evaluated while the generator is expected to provide correct
voltage and frequency. That means the alarms start to be evaluated after transition form
Idle
to
Running
phase when the period of
Max stab time
has already elapsed, remain
beeing evaluated while the gen-set is running at nominal speed (regardless of GCB
position) and stop to be evaluated by transition to the
Cooling
phase.