IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
235
The output can be used for indication of the MCB position.
Binary output: Bank params OK
Related FW
3.0
Description
This output indicates that the bank actually provides proper voltage and
frequency. The output is closed while the bank of gen-sets is running (regardless
of whether BCB is closed or not) and
all bank electrical parameters
are in limits.
Binary output: Bus Params OK
Related FW
3.0
Description
This output indicates that the bus is healthy. The output is closed while
all bus
electrical parameters
are in limits.
Binary output: kWh pulse
Related FW
3.0
Description
This output generates 100ms pulse always when the internal kWh counter
incremented.
Binary output: In synchronism
Related FW
3.0
Description
This output is closed
during synchronization
when all synchro conditions have
been fulfilled. The output is opened either when:
•
the synchro conditions are lost
or
•
the corresponding breaker has been closed
or
•
the sychronizing was interrupted or timed out.
Synchro conditions are following:
•
Phase shift between generator and mains (bus) voltage must be within
range of ±
for period longer than
•
Voltage difference between generator and mains (bus) voltage (in all
phases) must be lower or equal to
The output is intended for manual synchronization. Automatic closing of GCB
must be disabled
for this case. Use the input