IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
230
Description
The output is closed while the
actual reserve
is above the reserve for start from
the
reserve set #3
.
Binary output: Syst res 4 OK
Related FW
3.0
Description
The output is closed while the
actual reserve
is above the reserve for start from
the
reserve set #4
.
Binary output: AllAvailGS run
Related FW
3.0
Description
The output is closed while all gen-sets in the group, which participate in the
, are running and loaded.
Binary output: Vbus <>
Related FW
3.0
Description
The output is closed while the
generator over/under voltage
alarm is present in the
alarm list.
Binary output: Vbus <>
Related FW
3.0
Description
The output is closed while the
bus over/under voltage
alarm is present in the
alarm list.
Binary output: Overcurrent
Related FW
3.0
Description
The output is closed while there is either the
Generator IDMT Overcurrent
or
Generator Short current
alarms present in the alarm list.
Binary output: Common Wrn
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Warning
type present
in the alarm list. The alarm can be in any state, i.e. active unconfirmed, active
confirmed or inactive unconfirmed. See the chapter
Alarm management
for more
information.