Alarm output: Overspeed
Related FW
3.0
Description
This output is closed while the
Overspeed
alarm is present in the alarm list.
Alarm output: Underspeed
Related FW
3.0
Description
This output is closed while the
Underspeed
alarm is present in the alarm list.
Alarm output: Start fail
Related FW
3.0
Description
This output is closed while the
Start fail
alarm is present in the alarm list. See the
diagram in the description of the
output for information when the start fail
alarm is indicated.
Alarm output: Sd Stop fail
Related FW
3.0
Description
This output is closed while the
Sd Stop fail
alarm is present in the alarm list. This
alarm appears when the gen-set indicates that it is rotating although it has to be
stopped. This situation can occur:
•
when the gen-set starts to rotate spontaneously (from the controller point
of view) or
•
when the gen-set does not stop after the stop command has been issued.
See the timing diagram in the description of the output
Alarm output: ChrgAlternFail
Related FW
3.0
Description
This output is closed while the
ChrgAlternFail
alarm is present in the alarm list.
This alarm appears when the voltage at the controller D+ terminal drops below
90% of the controller supply voltage for more than 2s.
N
OTE
:
Function of the D+ terminal is selected by the setpoint
D+ Function
.
Alarm output: Pickup fail
Related FW
3.0
Description
This output is closed while the
ChrgAlternFail
alarm is present in the alarm list.