IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
185
stop function, which means disconnecting power supply from the controller
outputs.
Binary input: REMOTE: Remote oOFF
Related FW
3.0
Description
The controller is forced into OFF mode while this input is active and the genset is
not running. The controller will return into the previous mode after the input is
deactivated. If the genset is running, the mode does not change until it is stopped.
Use this input if you need to disable the genset temporarily from any reason
(maintenance, control from a higher-level automation system etc..).
Binary input: REMOTE: Remote MAN
Related FW
3.0
Description
The controller is forced into MAN mode while this input is active.
N
OTE
:
Programming of firmware and/or configuration is disabled while this input is active,
as the programming is allowed in OFF mode only and GenConfig is not able to
switch the controller to OFF mode while MAN mode is forced by this input.
Binary input: REMOTE: Remote AUT
Related FW
3.0
Description
The controller is forced into AUT mode while this input is active.
N
OTE
:
Programming of firmware and/or configuration is disabled while this input is active,
as the programming is allowed in OFF mode only and GenConfig is not able to
switch the controller to OFF mode while AUT mode is forced by this input.
Binary input: AccessLock int
Related FW
3.0
Description
This input forces the controller
built-in
terminal into monitoring mode.
•
Setpoints changes are disabled.
•
Using control buttons on the panel is disabled even if the controller is in
MAN mode.
•
Change of controller mode is disabled.
N
OTE
:
As the IS-NT and IGS-NT-BB do not have built-in terminal, this input is assigned
to the terminal or IntelliVision (display) #1, which is supposed to be directly
attached to the controller or mounted close to it.
Binary input: AccessLock ext
Related FW
3.0