IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
183
Value: PulseCounter 2
Group
Statistics
Units
-
Related FW
3.0
Description
This is the value of
PulseCounter #2
module. See the binary input
N
OTE
:
Available in IS-NT only.
Value: PulseCounter 3
Group
Statistics
Units
-
Related FW
3.0
Description
This is the value of
PulseCounter #3
module. See the binary input
N
OTE
:
Available in IS-NT only.
Value: PulseCounter 4
Group
Statistics
Units
-
Related FW
3.0
Description
This is the value of
PulseCounter #4
module. See the binary input
N
OTE
:
Available in IS-NT only.
Table of binary input functions
Binary input: BCB feedback
Related FW
3.0
Description
This input is used for connection of the normally open feedback contact from the
bank circuit breaker or contactor. If the input is active, the controller will consider
the BCB as closed and vice versa.
•
If the feedback does not respond to a change of the control output
BCB Fail
will be issued.
•
If the feedback changes it's position unexpectedly without any command
given by the control output, the alarm
BCB Fail
will be issued immediately.
N
OTE
: