IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
196
Available in IS-NT only.
Binary input: PulseCounter 4
Related FW
3.0
Description
This is the input of the
PulseCounter #4
module. The module counts pulses at the
input and if the input pulses counter reaches value given by the setpoint
, the counter value
Statistic
) is
increased by 1 and input pulses conter is reset to 0. Both counter value and input
pulses counter are stored in the nonvolatile memory.
The
PulseCounter
modules are intended e.g. for connecting external energy or
fuel meters with pulse outputs.
N
OTE
:
Minimal pulse width as well as minimal pause between two succesive pulses is
100ms.
N
OTE
:
The counter value can be reset in the InteliMonitor statistics window.
N
OTE
:
Available in IS-NT only.
Binary input: Timer block 1
Related FW
3.0
Description
This input is used to disable temporarily the output from the
Timer channel #1
.
N
OTE
:
and output
N
OTE
:
See the chapter
Timers
for more details about timers.
Binary input: Timer block 2
Related FW
3.0
Description
This input is used to disable temporarily the output from the
Timer channel #2
.
N
OTE
:
and output
N
OTE
:
See the chapter
Timers
for more details about timers.
Binary input: Timer block 3
Related FW
3.0