Emotron VS Series Quick Start Guide
- 109 -
C2.08
Minimum input of curve AI2
Range:0.0%
~
input of inflection
point1 of curve AI2
Default:1.0%
C2.09
Set value corresponding to
minimum input of curve AI2
Range:-100.0
~
100.0%
Default:0.0%
C2.10
Input of inflection point
1 of curve AI2
Range: Minimum input of curve
AI2
~
Input of inflection point 2
of curve AI2
Default:
100.0%
C2.11
Set value corresponding
to input of inflection
point 1 of curve AI2
Range:-100.0
~
100.0%
Default:
100.0%
C2.12
Input of inflection point
2 of curve AI2
Range: Input of inflection point 1
of curve AI2
~
Maximum input
of curve AI2
Default:
100.0%
C2.13
Set value corresponding
to input of inflection
point 2 of curve AI2
Range:-100.0
~
100.0%
Default:
100.0%
C2.14
Maximum input of curve
AI2
Range: Input of inflection point 2
of curve AI2
~
100.0%
Default:100.0%
C2.15
Set value corresponding to
maximum input of curve AI2
Range:-100.0
~
100.0%
Default:100.0%
C2.16
Minimum input of curve
AI3
(VSX Only)
Range:0.0%
~
input of inflection
point1 of curve AI3
Default:0.0%
C2.17
Set value corresponding to
minimum input of curve AI3
(VSX Only)
Range:-100.0
~
100.0%
Default:-100.0
%
C2.18
Input of inflection point
1 of curve AI3
(VSX Only)
Range: Minimum input of curve
AI3
~
Input of inflection point 2
of curve AI3
Default:25.0%
C2.19
Set value corresponding
to input of inflection
point 1 of curve AI3
(VSX Only)
Range:-100.0
~
100.0%
Default:-50.0%
C2.20
Input of inflection point
2 of curve AI3
(VSX Only)
Range: Input of inflection point 1
of curve AI3
~
Maximum input
of curve AI3
Default:75.0%
C2.21
Set value corresponding
to input of inflection
point 2 of curve AI3
(VSX Only)
Range:-100.0
~
100.0%
Default:50.0%
C2.22
Maximum input of curve AI3
(VSX Only)
Range: Input of inflection point 2
of curve AI3
~
100.0%
Default:100.0%
C2.23
Set value corresponding to
maximum input of curve AI3
(VSX Only)
Range:-100.0
~
100.0%
Default:100.0%
Curve AI2 is defined by C2.08
~
C2.15. Curve AI3 is defined by C2.16
~
C2.23. The usage of
curve AI2 and curve AI3 is the same as that of curve AI1.
C2.24
Minimum input of curve
keypad potentiometer
Range:0.0
~
Maximum input of
curve keypad potentiometer
Default:0.5%
C2.25
Set value corresponding to
minimum input of curve
keypad potentiometer
Range:-100.0
~
100.0%
Default:0.0%
C2.26
Maximum input of curve
keypad potentiometer
Range: Minimum input of curve
keypad potentiometer
~
100.0%
Default:99.9%
C2.27
Set value corresponding to
Range:-100.0
~
100.0%
Default:100.0%