Emotron VS Series Quick Start Guide
- 102 -
C0.16
Terminal UP/DOWN frequency
adjustment treatment
Range:00000
~
11111
Default:00000
Unit's place: action when stop
0: Clear
Terminal UP/DOWN frequency adjustment value is cleared when the drive stops.
1: Holding
Terminal UP/DOWN frequency adjustment value is maintained when the drive stops.
Ten's place: action on power loss
0: Clear
Terminal UP/DOWN frequency adjustment value is cleared in case of power loss.
1: Holding
Terminal UP/DOWN frequency adjustment value is saved in case of power loss.
Hundred's place: integral function
0: No integral function
Adjustment step size is kept constant during terminal UP/DOWN adjustment, in compliance with
C0.17.
1: Integral function enabled
When frequency is adjusted through terminal UP/DOWN, initial step size is set by C0.17.With the
effective lasting time of the terminals, adjustment step size will increase gradually.
Thousand
’
s place: UP/DOWN frequency adjust selection
0: Can’t be reduced to negative frequency
When adjusted by terminal UP/DOWN, frequency can’t be reduced to negative value
1:Can be reduced to negative frequency
When adjusted by terminal UP/DOWN, frequency can be reduced to negative value
Ten thousand
’
s place: Jog function to clear UP/DOWN
0: Not clear
1: Clear
C0.17
Terminal UP/DOWN
frequency change step size
Range:0.00
~
50.00Hz
Default:1.00Hz/200ms
It is used to adjust the rate of change of frequency when the frequency is adjusted by means of
terminal UP/DOWN.
C0.18
Power on running terminal
action selection
Range: 0
~
1
Default: 0
It is only valid to running command terminal which is set in number 1,2,4,5(Running forward,
running reverse, JOG forward, JOG reverse), and only valid for the first running after power on.
0: Electrial level effective
When terminal is given running command, running terminal is detected to be ON, inverter start to
run. Please ensure the terminal statue before power on.
1: Edge t Electrical level effective(When power on)
When terminal is given running command, the terminal is detected to jump from OFF to ON and
maintain ON, inverter start to run.
2: Edge t Electrical level effective(Every start)
When terminal is given running command, the terminal is detected to jump from OFF to ON and
maintain ON, inverter start to run.
Group C1 Digital Output
C1.00
Y1 output function
Range:0
~
99
Default:1
C1.01
Y2/HO output function
(VSX Only)
(when used as Y2)
Range:0
~
99
Default:3
C1.02
Relay 1 output function
Range:0
~
99
Default:2
C1.03
Relay 2 output function
(VSX Only)
Range:0
~
99
Default:11
Define the functions of digital output terminals Y1 & Y2, relay 1 and relay 2.Output terminal
function selections are as follows: