Emotron VS Series Quick Start Guide
- 137 -
C0.00
~
C0.06=32
(Counting pulses)
C0.00
~
C0.06=33
(Counting reset)
U0.28
(Counting value)
F2.08
(Designated
counting value)
≥
C1.00
~
C1.03=17
(Designated
counting value reached)
Counting pulses
Counting reset
Clear to 0
Reset
After the designated
counting value is
reached, set the DO
terminal to 1.
Counting pulses input
Counting reset input
Designated counting
value reached output
1
2
3
F2.08=6
U0.28=6
4
5
6
≥
F2.09
(Set counting
value)
C1.00
~
C1.03=18
(Set counting
value reached)
After the set counting
value is reached, set
the DO terminal to 1.
Reset
Set counting value
reached output
F2.08=9
U0.28=9
7
8
9
U0.28=0
Fig 6-36 Reaching the set count value and designated count value
ATTENTION:
Actual count value can be cleared through digital input terminal "count clear".
Actual count value is saved at power loss.
F2.10
Wake up frequency
Range: Dormancy
frequency
~
Fmax
Default: 0.00Hz
F2.11
Wake up delay time
Range: 0.0
~
6000.0s
Default: 0.0s
F2.12
Dormancy frequency
Range: 0.00
~
Wake up
frequency
Default: 0.00Hz
F2.13
Dormancy delay time
Range: 0.0
~
6000.0s
Default: 0.0s
F2.17
Wake up pressure
Range: 0.0%
~
Dormancy
pressure
Default: 10.0%
F2.18
Dormancy pressure
Range: Wake up
pressure
~
100.0%
Default: 50.0%
The parameters are used for the dormancy and wake up function in water supply application
During inverter operation, when F2.15 set to be “0”, and when setting frequency is lower than
F2.12, after delay time of F2.13, inverter entry dormancy and stop. When F2.15 set to be “1”, and
when pressure feedback is bigger than F2.18, after delay time of F2.13, inverter entry dormancy and
stop
During inverter dormancy, when F2.14 set to be “0”, and when setting frequency is bigger than
F2.10, after delay time of F2.11, inverter start to operate; When F2.14 set to be “1”, and when pressure
feedback is lower than F2.17, after delay time of F2.11, inverter start to operate
Usually, please set wake up frequency bigger than dormancy frequency. If wake up frequency and
dormancy frequency are set to be 0.00Hz, wake up and dormancy function is invalid.
When start dormancy function, if frequency source is PID, need to set F0.26 to be “1” PID
operation at stop
F2.14
Wake up mode selection
Range: 0
~
1
Default: 0
0: Frequency
When inverter in dormancy, wake up mode is frequency wake up
1: Pressure
When inverter in dormancy, wake up mode is pressure wake up
F2.15
Dormancy mode selection
Range: 0
~
1
Default: 0
0: Frequency
Inverter dormancy mode is frequency dormancy
1: Pressure
Inverter dormancy mode is pressure dormancy