Emotron VS Series Quick Start Guide
- 67 -
E0.11
Protection action 2
Unit’s place: External equipment
fault (Err13)
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue to
run
00000
×
Ten's place: EEPROM read/write
fault (Err15)
(Same as unit's place)
Hundred's place: Communication
overtime error (Err18)
(Same as unit's place)
Thousand's place: PID feedback
loss (Err19)
(Same as unit's place)
Ten thousand's place: Continuous
running time reached (Err20) (Same
as unit's place)
E0.12
Protection action 3
Unit's place: Module temperature
detection disconnection
(
Err24)
0: Fault reported and coast to
stop
1: Stop according to the stop
mode
2: Fault reported but continue to
run
3: Fault protection disabled
00030
×
Ten's place: Load becoming 0
(Err25) (Same as unit's place)
E0.14
Frequency selection for
continuing to run upon fault
0: Current running frequency
1
×
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
E0.15
Backup frequency upon
abnormality
0.00
~
Fmax
0.00Hz
×
E0.17
Motor overload protection
time
30.0
~
300.0s
60.0s
×
E0.18
Overload alarm
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
00010
×
Ten's place: compared object
0: Rated current of motor
1: Rated current of drive
Hundred’s place: Fault reported
0:No fault reported
1:Fault reported
Thousand’s place: whether to
decelerate or not when overload
alarm
0: No deceleration
1: Deceleration
Ten thousand's place: given mode
for overload threshold