Emotron VS Series Quick Start Guide
- 136 -
F2.05
Set length
Range:0
~
65535m
Default:1000m
F2.06
Number of pulses per meter
Range:0.0
~
6553.5
Default:100.0
The preceding parameters are used for fixed length control.
The length information is collected by DI terminals. U0.27 (Actual length) is calculated by dividing
the number of pulses collected by the DI terminal by F2.06 (Number of pulses each meter). When the
actual length U0.27 exceeds the set length in F2.05, the DO terminal allocated with function (Length
reached) becomes ON. During the fixed length control, the length reset operation can be performed
via the DI terminal allocated with function 35. For details, see the descriptions of C0.00 to C0.09.
Allocate corresponding DI terminal with function 34 (Length count input) in applications. If the
pulse frequency is high, DI7/HI must be used.
F2.06=34
(Length pulses
input)
F2.00
~
F2.06=35
(Length reset)
÷
F2.16
(Number of pulses
parameter)
U0.29
(Actual length)
F2.15
(Set length)
≥
C1.00
~
C1.03=19
(Length reached)
Length pulses input
Length reset
Clear to 0
Reset
After the length is
reached, the DO
becomes 1.
Length pulses input
Length reset input
Length reached output
1
2
3
F2.15=6
U0.27=6
4
5
6
U0.27=0
Fig
6-35
F2.07
Command when the length
attained
Range:0
~
1
Default: 0
0: Not stop
1: Stop
This parameter sets the action of the drive when actual length attains the length set by F2.05.
Actual length can be cleared through digital input terminal "length clear".
ATTENTION:
When actual length is detected to attain the set length, digital output terminal "length attained"
outputs ON signal no matter the drive is set to stop or not stop.
Actual length is saved at power loss and can be read in both stop and running.
F2.08
Set count value
Range:1
~
65535
Default:1000
F2.09
Designated count value
Range:1
~
65535
Default:1000
The count value needs to be collected by DI terminal. Allocate the corresponding DI terminal with
function 32 (Counter input) in applications. If the pulse frequency is high, DI7/HI must be used.
When the count value reaches the set count value (F2.08), the DO terminal allocated with function
17 (Set count value reached) becomes ON. Then the counter stops counting.
When the counting value reaches the designated counting value (F2.09), the DO terminal
allocated with function 17 (Designated count value reached) becomes ON. Then the counter continues
to count until the set count value is reached.
F2.09 should be equal to or smaller than F2.08.
Figure 6-36 Reaching the set count value and designated count value