Emotron VS Series Quick Start Guide
- 103 -
Setting
Corresponding
function
Description
0
No output
Output terminal is disabled, and there is no output.
1
Drive is running
The output is ON when the drive is running, and output
is OFF when drive stopped.
2
Fault output
When the drive is in fault, outputs ON.
3
Frequency-level
detection FDT1
output
Refer to the descriptions of C1.10 and C1.11.
4
Frequency-level
detection FDT2
output
Refer to the descriptions of C1.12 and C1.13.
5
Drive in 0Hz
running 1(no output
at stop)
When be running at 0Hz, this corresponding terminal
outputs ON signal. During stop no ON signal will be
generated.
6
Drive in 0Hz
running 2(output at
stop)
Outputs ON signal when is running at 0Hz and also
outputs ON signal at stop.
7
Upper limit
frequency attained
When output frequency attains b0.09 (upper limit
frequency), outputs ON.
8
Lower limit
frequency attained
(no output at stop)
When output frequency attains b0.10 (lower limit
frequency), outputs ON. In the stop state, the terminal
becomes OFF.
9
Frequency attained
Refer to the descriptions of C1.09.
10
Ready for RUN
If the AC drive main circuit and control circuit become
stable, and the AC drive detects no fault and is ready for
RUN, the terminal becomes ON.
11
Drive (motor)
overloaded alarm
In case drive output current exceeds E0.19 (overload
alarm threshold) and its duration exceeds E0.20 (overload
alarm activated time that exceeds threshold), ON signal is
generated. Refer to parameters E0.18
~
E0.20 for
information with regard to drive (motor) overloaded alarm.
12
Drive overheat
alarm
When drive internally detected temperature exceeds
E0.21 (Drive overheat alarm threshold), ON signal will be
output.
13
Current running
time attained
When current running time attains the value of C1.14,
corresponding terminal outputs ON. Current running time is
cleared when drive stops.
14
Accumulative
power-on time
attained
When accumulative power-on time attains the value of
C1.15, corresponding terminal outputs ON. Accumulative
power-on time is maintained when stopped.
15
Accumulative
running time
attained
When accumulative running time attains the value of
C1.16, corresponding terminal outputs ON. Accumulative
running time is maintained when stopped.
16
PLC cycle
completed
Upon the completion of a cycle of simple PLC running,
ON signal with a width of 250ms will be output.
17
Set count value
attained
The terminal becomes ON when the count value
reaches the value set in F2.07.
18
Designated count
value attained
The terminal becomes ON when the count value
reaches the value set in F2.08. Refer to the specification of
parameter F2.07 and F2.08.
19
Length attained
The terminal becomes ON when the detected actual
length
exceeds the value set in F2.04. Refer to the
specification of parameter F2.05
~
F2.07.
20
Under load alarm
When inverter detects underload, outputs ON signal