Emotron VS Series Quick Start Guide
- 99 -
DI2 is invalid
The four parameters set the delayed response time before DI1/DI2 is valid or invalid
ATTENTION:
Terminal delay time C0.11and C0.12 can be set with filtering time C0.10 at the same time. The
drive will respond after the signals via DI1 and DI2 go through filtering time, and then delay time.
Terminals DI3
~
DI7 have no delay time function.
C0.13
Terminal DI1
~
DI5
positive/negative logic
Range:00000
~
11111
Default:00000
These parameters are used to set the valid mode of DI terminals.
Unit's place: DI1
0: Positive logic
The DI terminal is valid when being connected with COM, and invalid when being disconnected
from COM.
1: Negative Logic
The DI terminal is invalid when being connected with COM, and invalid when being disconnected
from COM.
Ten's place: DI2 (same as DI1)
Hundred's place: DI3 (same as DI1)
Thousand's place: DI4 (same as DI1)
Ten thousand's place: DI5 (VSX Only) (same as DI1)
C0.14
Terminal DI6
~
AI3
positive/negative logic
Range:00000
~
11111
Default:00000
Unit's place: DI6(VSX Only)
0: Positive logic
The DI terminal is valid when being connected with COM, and invalid when being disconnected
from COM.
1: Negative Logic
The DI terminal is invalid when being connected with COM, and invalid when being disconnected
from COM.
Ten's place: DI7(VSX Only) (same as DI6)
Hundred's place: AI1
0: Positive logic ;< 3V, valid; > 7V, invalid
1: Negative Logic ;< 3V, invalid; > 7V, valid
Thousand's place: AI2 (same as AI1)
Ten thousand's place: AI3 (VSX Only)
0: Positive logic ;< -6V, valid; > 4V, invalid
1: Negative Logic ;< -6V, invalid; > 4V, valid
C0.15
Terminal command mode
Range:0
~
4
Default: 0
This parameter is used to set the mode in which the AC drive is controlled by external terminals.
The following uses DI1, DI2 and DI3 among DI1 to DI7 as an example, with allocating functions of DI1,
DI2 and DI3 by setting F4-00 to F4-02.
0: Two-line mode 1
It is the most commonly used two-line mode, in which the forward/reverse rotation of the motor is
decided by DI1 and DI2. The parameters are set as below:
Function Code
Parameter Name
Value
Function Description
C0.15
Terminal command mode
0
Two-line 1
C0.00
DI1 function selection
1
Forward RUN (FWD)
C0.01
DI2 function selection
2
Reverse RUN (REV)