217
SP__ (cont)
SP Reset Ratio
SPRRATIO
0.2
SP Reset Limit
SPRLIMIT
0.75
SP Reset Econo.Position
%
ECONOSPR
5
Stat.Pres.PID Run Rate
secs
SPIDRATE
7
Static Press. Prop. Gain
STATP_PG
0.5
Static Press. Intg. Gain
STATP_IG
0.5
Static Press. Derv. Gain
STATP_DG
0.3
SWLG
Power Fault Input - Good
Open/Close
PWRFLOGC
Close
Filter Status Inpt-Clean
Open/Close
FLTSLOGC
Open
Post Filter Stat. In-Cln
Open/Close
PFLTSLGC
Open
IGC Feedback - Off
Open/Close
GASFANLG
Open
RemSw Off-Unoc-Strt-NoOv
Open/Close
RMTINLOG
Open
Enthalpy Input - Low
Open/Close
ENTHLOGC
Close
Fan Status Sw. - Off
Open/Close
SFSLOGIC
Open
Dmd.Lmt.Sw.1 - Off
Open/Close
DMD_SW1L
Open
Dmd.Lmt.Sw.2 - Off
Open/Close
DMD_SW2L
Open
IAQ Disc.Input - Low
Open/Close
IAQINLOG
Open
Fire Shutdown - Off
Open/Close
FSDLOGIC
Open
Press. Switch - Off
Open/Close
PRESLOGC
Open
Evacuation Sw. - Off
Open/Close
EVACLOGC
Open
Smoke Purge Sw. - Off
Open/Close
PURGLOGC
Open
Dehumidify Sw. - Off
Open/Close
DHDISCLG
Open
SF Bypass Sw. - Off
Open/Close
SFBYLOGC
Open
PE Bypass Sw. - Off
Open/Close
PEBYLOGC
Open
TRIM
Air Temp Lvg SF Trim
deltaF
SAT_TRIM
0
RAT Trim
deltaF
RAT_TRIM
0
OAT Trim
deltaF
OAT_TRIM
0
SPT Trim
deltaF
SPT_TRIM
0
Limit Switch Trim
deltaF
LSW_TRIM
0
Air Tmp Lvg Evap Trim
deltaF
CCT_TRIM
0
A1 Discharge Temp Trim
deltaF
DTA1TRIM
0
Suction Gas Temp A Trim
deltaF
RGTATRIM
0
Cir. A EXV 1 Temp Trim
deltaF
CAX1TRIM
0
Cir. A EXV 2 Temp Trim
deltaF
CAX2TRIM
0
Cir. B EXV 1 Temp Trim
deltaF
CBX1TRIM
0
Cir. B EXV 2 Temp Trim
deltaF
CBX2TRIM
0
Suct.Press.Circ.A Trim
PSI
SPA_TRIM
0
Suct.Press.Circ.B Trim
PSI
SPB_TRIM
0
Dis.Press.Circ.A Trim
PSI
DPA_TRIM
0
Dis.Press.Circ.B Trim
PSI
DPB_TRIM
0
Bldg. Pressure Trim (ma)
BPMATRIM
0
Static Press. Trim (ma)
SPMATRIM
0
Outside Air CFM Trim(ma)
OAMATRIM
0
Supply Air CFM Trim (ma)
SAMATRIM
0
Return Air CFM Trim (ma)
RAMATRIM
0
Exh. Air CFM Trim (ma)
EAMATRIM
0
UNIT
Machine Control Type
CTRLTYPE
3
Unit Size (75 - 150)
UNITSIZE
150
Fan Mode (0=auto,1=cont)
FAN_MODE
0
Remote Switch Config
RMTINCFG
0
CEM Module installed
No/Yes
CEM_BRD
Yes
Liquid Sensors Installed
No/Yes
LQ_SENS
Yes
Power Monitor Installed
No/Yes
PWR_MON
No
VFD Bypass Enable?
No/Yes
VFD_BYEN
No
UV-C Lamp Config?
UVCL_CFG
0
Temp.Cmp.Strt.Cool Factr
mins
TCSTCOOL
0
Temp.Cmp.Strt.Heat Factr
mins
TCSTHEAT
0
Fan fail shuts down unit
No/Yes
SFS_SHUT
Yes
Fan Stat Monitoring Type
SFS_MON
0
VAV Unocc.Fan Retry Time
mins
SAMPMINS
50
MAT Calc Config
MAT_SEL
1
Reset MAT Table Entries?
No/Yes
MATRESET
No
MAT Outside Air Default
%
MATOAPOS
20
Altitude........in feet:
ALTITUDE
0
APPENDIX B
—
CCN TABLES (CONT)
SERVICE-CONFIG TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
DEFAULT
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...