205
APPENDIX A
—
LOCAL DISPLAY TABLES (CONT)
MODE — TIMECLOCK
ITEM
EXPANSION
RANGE
UNITS
CNN POINT
DEFAULTS
PAGE NO.
TIME
TIME OF DAY
HH.MM
Hour and Minute
00:00 to 23:59
TIME
DATE
MONTH,DATE,DAY AND YEAR
MNTH
Month of Year
multi text string
MOY
DOM
Day of Month
1 to 31
DOM
DAY
Day of Week
multi text string
DOWDISP
YEAR
Year
e.g. 2013
YOCDISP
SCH.L
LOCAL TIME SCHEDULE
PER.1
PERIOD 1
DAYS
DAY FLAGS FOR PERIOD 1
Period 1 only
MON
Monday in Period
No/Yes
PER1MON
Yes
TUE
Tuesday in Period
No/Yes
PER1TUE
Yes
WED
Wednesday in Period
No/Yes
PER1WED
Yes
THU
Thursday in Period
No/Yes
PER1THU
Yes
FRI
Friday in Period
No/Yes
PER1FRI
Yes
SAT
Saturday in Period
No/Yes
PER1SAT
Yes
SUN
Sunday in Period
No/Yes
PER1SUN
Yes
HOL
Holiday in Period
No/Yes
PER1HOL
Yes
OCC
Occupied from
0 to 6144
PER1_OCC
00:00
UNC
Occupied to
0 to 6144
PER1_UNC
24:00
Repeated for periods 2 to 8
HOL.L
LOCAL HOLIDAY SCHEDULES
HD.01
HOLIDAY SCHEDULE 01
MON
Holiday Start Month
0 to 12
HOL_MON1
DAY
Holiday Start Day
0 to 31
HOL_DAY1
LEN
Holiday Duration (Days)
0 to 99
HOL_LEN1
Repeated for holidays 2 to 30
DAY.S
DAYLIGHT SAVINGS TIME
DS.ST
DAYLIGHT SAVINGS START
ST.MN
Month
1 to 12
STARTM
3
ST.WK
Week
1 to 5
STARTW
2
ST.DY
Day
1 to 7
STARTD
7
MIN.A
Minutes to Add
0 to 90
MINADD
60
DS.SP
DAYLIGHTS SAVINGS STOP
SP.MN
Month
1 to 12
STOPM
11
SP.WK
Week
1 to 5
STOPW
1
SP.DY
Day
1 to 7
STOPD
7
MIN.S
Minutes to Subtract
0 to 90
MINSUB
60
MODE — OPERATING MODES
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
SYS.M
ascii string spelling out the system mode
string
HVAC
ascii string spelling out the hvac modes
string
CTRL
ascii string spelling out the "control type"
string
MODE
MODES CONTROLLING UNIT
OCC
Currently Occupied
Off/On
MODEOCCP
T.OVR
Timed Override in Effect
Off/On
MODETOVR
DCV
DCV Resetting Min Pos
Off/On
MODEADCV
SA.R
Supply Air Reset
Off/On
MODESARS
DMD.L
Demand Limit in Effect
Off/On
MODEDMLT
T.C.ST
Temp.Compensated Start
Off/On
MODETCST
IAQ.P
IAQ Pre-Occ Purge Active
Off/On
MODEIQPG
LINK
Linkage Active - CCN
Off/On
MODELINK
LOCK
Mech.Cooling Locked Out
Off/On
MODELOCK
H.NUM
HVAC Mode Numerical Form
0 to 40
MODEHVAC
MODE — ALARMS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
CURR
CURRENTLY ACTIVE ALARMS
this is a dynamic list of active alarms
R.CUR
Reset All Current Alarms
No/Yes
ALRESET
ram config
HIST
ALARM HISTORY
this is a record of the last 20 alarms
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...