214
DEHU (cont)
Condenser EXV Max Open
%
COND_MAX
40
LAT Sample Buffer Length
LAT_SAMP
10
LAT Sample Rate Seconds
secs
LAT_RATE
4
DISP
Metric Display
Off/On
DISPUNIT
Off
Language Selection
LANGUAGE
0
Password Enable
Disable/Enable
PASS_EBL
Enable
Service Password
PASSWORD
1111
Contrast Adjustment
CNTR_ADJ
0
Brightness Adjustment
BRTS_ADJ
0
DLVT
Dmd Level Lo Heat ON
deltaF
DMDLHON
1.5
Dmd Level(+) Hi Heat ON
deltaF
DMDHHON
0.5
Dmd Level(-) Lo Heat OFF
deltaF
DMDLHOFF
1
Dmd Level Lo Cool ON
deltaF
DMDLCON
1.5
Dmd Level(+) Hi Cool ON
deltaF
DMDHCON
0.5
Dmd Level(-) Lo Cool OFF
deltaF
DMDLCOFF
1
Cool Trend Demand Level
deltaF
CTRENDLV
0.1
Heat Trend Demand Level
deltaF
HTRENDLV
0.1
Cool Trend Time
secs
CTRENDTM
120
Heat Trend Time
secs
HTRENDTM
120
DMDL
Demand Limit Select
DMD_CTRL
0
Demand Limit at 20 ma
%
DMT20MA
100
Loadshed Group Number
SHED_NUM
0
Loadshed Demand Delta
%
SHED_DEL
0
Maximum Loadshed Time
mins
SHED_TIM
60
Demand Limit Sw.1 Setpt.
%
DLSWSP1
80
Demand Limit Sw.2 Setpt.
%
DLSWSP2
50
ECON
Economizer Installed ?
No/Yes
ECON_ENA
Yes
Economizer Min.Position
%
ECONOMIN
5
Economizer Max.Position
%
ECONOMAX
98
Economzr trim for sumZ ?
No/Yes
ECONTRIM
Yes
Econ ChangeOver Select
ECON_SEL
0
OA Enthalpy ChgOvr Selct
OAEC_SEL
4
Outdr.Enth Compare Value
OAEN_CFG
24
High OAT Lockout Temp
degF
OAT_LOCK
60
OA Dewpoint Temp Limit
degF
OADEWCFG
55
Outside Air RH Sensor
Disable/Enable
OARHSENS
Disable
Outdoor Air CFM Sensor
Disable/Enable
OCFMSENS
Disable
Economizer Min.Flow
CFM
OACFMMAX
2000
IAQ Demand Vent Min.Flow
CFM
OACFMMIN
0
Econ.Min.Flow Deadband
CFM
OACFM_DB
400
Economizer Prop.Gain
EC_PGAIN
1
Economizer Range Adjust
deltaF
EC_RANGE
2.5
Economizer Speed Adjust
EC_SPEED
0.75
Economizer Deadband
deltaF
EC_DBAND
0.5
Unoc Econ Free Cool Cfg
UEFC_CFG
0
Unoc Econ Free Cool Time
mins
UEFCTIME
120
Un.Ec.Free Cool OAT Lock
degF
UEFCNTLO
50
Econ 1 Out Ser Number 1
ECN1_SN1
0
Econ 1 Out Ser Number 2
ECN1_SN2
0
Econ 1 Out Ser Number 3
ECN1_SN3
0
Econ 1 Out Ser Number 4
ECN1_SN4
0
Ecn1 Out Ctl Angl Lo Lmt
ECONCALM
85
Econ 2 Ret Ser Number 1
ECN2_SN1
0
Econ 2 Ret Ser Number 2
ECN2_SN2
0
Econ 2 Ret Ser Number 3
ECN2_SN3
0
Econ 2 Ret Ser Number 4
ECN2_SN4
0
Ecn2 Ret Ctl Angl Lo Lmt
ECN2CALM
85
Econ 3 Out Ser Number 1
ECN3_SN1
0
Econ 3 Out Ser Number 2
ECN3_SN2
0
Econ 3 Out Ser Number 3
ECN3_SN3
0
Econ 3 Out Ser Number 4
ECN3_SN4
0
Ecn3 Out Ctl Angl Lo Lmt
ECN3CALM
85
APPENDIX B
—
CCN TABLES (CONT)
SERVICE-CONFIG TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
DEFAULT
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...