190
APPENDIX A
—
LOCAL DISPLAY TABLES (CONT)
MODE
—
SERVICE TEST
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
PAGE NO.
TEST
Service Test Mode
Off/On
MAN_CTRL
STOP
Local Machine Disable
No/Yes
UNITSTOP
config
S.STP
Soft Stop Request
No/Yes
SOFTSTOP
forcible
FAN.F
Supply Fan Request
No/Yes
SFANFORC
forcible
INDP
TEST INDEPENDENT OUTPUTS
HUM.R
Humidifier Relay
Off/On
HUMR_TST
ALRM
Remote Alarm / Aux Relay
Off/On
ALRM_TST
FANS
TEST FANS
F.MOD
Fan Test Mode Automatic?
No/Yes
FANAUTO
E.POS
Econ 1 Out Act.Cmd.Pos.
0 to 100
%
ECONFANS
SF.BY
Supply Fan Bypass Relay
Off/On
SFBY_TST
S.VFD
Supply Fan Commanded %
0 to 100
%
SFVFDTST
PE.BY
Power Exhaust Bypass Rly
Off/On
PEBY_TST
E.VFD
Exhaust Fan Commanded %
0 to 100
%
EFVFDTST
A.VFD
MtrMaster A Commanded %
0 to 100
%
OAVFDTST
B.VFD
MtrMaster B Commanded %
0 to 100
%
OBVFDTST
CDF.1
Condenser Fan Output 1
Off/On
CDF1_TST
CDF.2
Condenser Fan Output 2
Off/On
CDF2_TST
CDF.3
Condenser Fan Output 3
Off/On
CDF3_TST
CDF.4
Condenser Fan Output 4
Off/On
CDF4_TST
CDF.5
Condenser Fan Output 5
Off/On
CDF5_TST
AC.T.C
CALIBRATE TEST-ACTUATORS
EC1.C
Econ 1 Out Act.Cmd.Pos.
0 to 100
%
ECON1TST
E1.CL
Economizer Calibrate Cmd
No/Yes
ECONOCAL
E1C.A
Econ 1 Out Act Ctl Angle
0 to 100
ECONCANG
EC2.C
Econ 2 Ret Act.Cmd.Pos.
0 to 100
%
ECON2TST
E2.CL
Economzr 2 Calibrate Cmd
No/Yes
ECON2CAL
E2C.A
Econ 2 Ret Act Ctl Angle
0 to 100
ECN2CANG
EC3.C
Econ 3 Out Act.Cmd.Pos.
0 to 100
%
ECON3TST
E3.CL
Economzr 3 Calibrate Cmd
No/Yes
ECON3CAL
E3C.A
Humidifier Act.Ctrl.Ang.
0 to 100
HUMDCANG
HTC.C
Ht.Coil Command Position
0 to 100
%
HTCLACTS
HT.CL
Heating Coil Act.Cal.Cmd
No/Yes
HCOILCAL
HTC.A
Heat Coil Act.Ctl.Angle
0 to 100
HTCLCANG
HMD.C
Humidifier Command Pos.
0 to 100
%
HUMD_TST
HM.CL
Humidifier Act. Cal. Cmd
No/Yes
HUMIDCAL
HMD.A
Humidifier Act.Ctrl.Ang.
0 to 100
HUMDCANG
HTC.3
Ht.Coil Command Position
0 to 100
HTC3ACTS
HC.3L
Heat Coil Act 3 Cal Cmd
No/Yes
HTC3_CAL
HC3.A
Heat Coil Act 3 Cal Cmd
0 to 100
HTC3CANG
HTC.4
Ht.Coil Command Position
0 to 100
HTC4ACTS
HC.4L
Heat Coil Act 4 Cal Cmd
No/Yes
HTC4_CAL
HC4.A
HTC4 Control Angle
0 to 100
HTC4CANG
SRCH
SEARCH FOR SERIAL NUMBER
ACTV
Belimo Serial Num Search
No/Yes
BELSERCH
ECN.1
Economizer 1 Search
No/Yes
EC1SERCH
forcible
ECN.2
Economizer 2 Search
No/Yes
EC2SERCH
forcible
ECN.3
Economizer 3 Search
No/Yes
EC3SERCH
forcible
HT.CL
Heat Coil Valve Search
No/Yes
HTCSERCH
forcible
HUMD
Humidifier Valve Search
No/Yes
HUMSERCH
forcible
HT.C3
Heat Coil 3 Valve Search
No/Yes
HTC3SRCH
HT.C4
Heat Coil 4 Valve Search
No/Yes
HTC4SRCH
HMZR
TEST HUMIDIMIZER
RHV
HumidiMizer 3-way Valve
Off/On
RHVH_TST
C.EXV
Condenser EXV Position
0 to 100
%
CEXVHTST
B.EXV
Bypass EXV Position
0 to 100
%
BEXVHTST
C.CAL
Condenser EXV Calibrate
Off/On
CEXV_CAL
B.CAL
Bypass EXV Calibrate
Off/On
BEXV_CAL
EXVS
TEST CIRCUIT EXVS
A1.EX
Circuit A EXV 1 Position
0 to 100
%
A_X1_TST
A2.EX
Circuit A EXV 2 Position
0 to 100
%
A_X2_TST
B1.EX
Circuit B EXV 1 Position
0 to 100
%
B_X1_TST
B2.EX
Circuit B EXV 2 Position
0 to 100
%
B_X2_TST
A1.CL
Cir A EXV 1 Calibrate
Off/On
A_X1_CAL
A2.CL
Cir A EXV 2 Calibrate
Off/On
A_X2_CAL
B1.CL
Cir B EXV 1 Calibrate
Off/On
B_X1_CAL
B2.CL
Cir B EXV 2 Calibrate
Off/On
B_X2_CAL
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...