APPENDIX A
—
LOCAL DISPLAY TABLES (CONT)
MODE — CONFIGURATION
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type
1 to 4
CTRLTYPE
3
SIZE
Unit Size (75 - 150)
75 to 150
UNITSIZE
75
FN.MD
Fan Mode (0=Auto, 1=Cont)
0 to 1
FAN_MODE
1
RM.CF
Remote Switch Config
0 to 3
RMTINCFG
0
CEM
CEM Module Installed
No/Yes
CEM_BRD
No
LQ.SN
Liquid Sensors Installed
No/Yes
LQ_SENS
No
PW.MN
Power Monitor Installed
No/Yes
PWR_MON
No
VFD.B
VFD Bypass Enable?
No/Yes
VFD_BYEN
No
SM.MN
Enable Smart Menus?
Disable/Enable
SMART_MN
Enable
TCS.C
Temp.Cmp.Strt.Cool Factr
0 to 60
Minute
TCSTCOOL
0
TCS.H
Temp.Cmp.Strt.Heat Factr
0 to 60
Minute
TCSTHEAT
0
SFS.S
Fan fail shuts down unit
No/Yes
SFS_SHUT
No
SFS.M
Fan Stat Monitoring Type
0 to 2
SFS_MON
0
VAV.S
VAV Unocc.Fan Retry Time
0 to 720
Minute
SAMPMINS
50
MAT.S
MAT Calc Config
0 to 2
MAT_SEL
1
MAT.R
Reset MAT Table Entries?
No/Yes
MATRESET
No
MAT.D
MAT Outside Air Default
0 to 100
%
MATOAPOS
20
ALTI
Altitude........in feet:
-1000 to 60000
ALTITUDE
0
DLAY
Startup Delay Time
0 to 900
DELAY
0
AUX.R
Auxiliary Relay Config
0 to 3
Seconds
AUXRELAY
0
SENS
INPUT SENSOR CONFIG
SPT.S
Space Temp Sensor
Disable/Enable
SPTSENS
Disable
SP.O.S
Space Temp Offset Sensor
Disable/Enable
SPTOSENS
Disable
SP.O.R
Space Temp Offset Range
1 to 10
dF
SPTO_RNG
5
SRH.S
Space Air RH Sensor
Disable/Enable
SPRHSENS
Disable
RRH.S
Return Air RH Sensor
Disable/Enable
RARHSENS
Disable
MRH.S
Mixed Air RH Sensor
Disable/Enable
MARHSENS
Disable
FACT
FACTORY CONFIGURATION
MD.MN
Model Number
MODEL_NM
F.RST
Perform Factory Restore?
0 to 1
FACT_RST
0
COOL
COOLING CONFIGURATION
A1.EN
Enable Compressor A1
Disable/Enable
CMPA1ENA
Enable
A2.EN
Enable Compressor A2
Disable/Enable
CMPA2ENA
Enable
A3.EN
Enable Compressor A3
Disable/Enable
CMPA3ENA
Enable
A4.EN
Enable Compressor A4
Disable/Enable
CMPA4ENA
Enable
B1.EN
Enable Compressor B1
Disable/Enable
CMPB1ENA
Enable
B2.EN
Enable Compressor B2
Disable/Enable
CMPB2ENA
Enable
B3.EN
Enable Compressor B3
Disable/Enable
CMPB3ENA
Enable
B4.EN
Enable Compressor B4
Disable/Enable
CMPB4ENA
Enable
CS.A1
CSB A1 Feedback Alarm
Disable/Enable
CSB_A1EN
Enable
CS.A2
CSB A2 Feedback Alarm
Disable/Enable
CSB_A2EN
Enable
CS.A3
CSB A3 Feedback Alarm
Disable/Enable
CSB_A3EN
Enable
CS.A4
CSB A4 Feedback Alarm
Disable/Enable
CSB_A4EN
Enable
CS.B1
CSB B1 Feedback Alarm
Disable/Enable
CSB_B1EN
Enable
CS.B2
CSB B2 Feedback Alarm
Disable/Enable
CSB_B2EN
Enable
CS.B3
CSB B3 Feedback Alarm
Disable/Enable
CSB_B3EN
Enable
CS.B4
CSB B4 Feedback Alarm
Disable/Enable
CSB_B4EN
Enable
Z.GN
Capacity Threshold Adjust
0.1 to 10
Z_GAIN
1.0
DT.GN
SUMZ EDT Derivative Gain
0.1 to 3
DTGAIN
1.5
MC.LO
Compressor Lockout Temp
-25 to 55
dF
OATLCOMP
40
LLAG
Lead/Lag Configuration
0 to 2
LEAD_LAG
0
HC.EV
High Capacity Evaporator
No/Yes
HCAPEVAP
No
H.ODF
High Efficiency OD Fans?
No/Yes
HIGH_EFF
No
M.M
Motor Master Control ?
No/Yes
MOTRMAST
No
MM.OF
MM Setpoint Offset
-20 to 20
dF
MMSPOFST
-10.0
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...