102
Table 71 —
Time Clock Menu
Daylight Savings Start Day (DS.ST
ST.DY)
This is the start day of the week for daylight savings. The day
can be set from 1 to 7 (Sunday=1, Monday=2, etc.).
Daylight Savings Minutes To Add (DS.ST
MIN.A)
This is the amount of time that will be added to the time clock
for daylight savings.
DAYLIGHT SAVINGS STOP (
DS.SP
)
This submenu configures the end date and time for daylight
savings.
Daylight Savings Stop Month (DS.SP
SP.MN)
This is the stop month for daylight savings time. The numbers
1 to 12 correspond to the months of the year (e.g., January = 1).
Daylight Savings Stop Week (DS.SP
SP.WK)
This is the stop week of the month for daylight savings. The
week can be set from 1 to 5.
Daylight Savings Stop Day (DS.SP
SP.DY)
This is the stop day of the week for daylight savings. The day
can be set from 1 to 7 (Sunday=1, Monday=2, etc.).
Daylight Savings Minutes To Subtract (DS.SP
MIN.S)
This is the amount of time that will be removed from the time
clock after daylight savings ends.
ITEM
EXPANSION
RANGE
CCN POINT
DEFAULT
TIME
TIME OF DAY
HH.MM
Hour and Minute
00:00
TIME
DATE
MONTH,DATE,DAY AND YEAR
MNTH
Month of Year
multi-text strings
MOY
DOM
Day of Month
0-31
DOM
DAY
Day of Week
multi-text strings
DOWDISP
YEAR
Year
e.g. 2003
YOCDISP
SCH.L
LOCAL TIME SCHEDULE
PER.1
PERIOD 1
PER.1
DAYS
DAY FLAGS FOR PERIOD 1
Period 1 only
PER.1
DAYS
MON
Monday in Period
No/Yes
PER1MON
Yes
PER.1
DAYS
TUE
Tuesday in Period
No/Yes
PER1TUE
Yes
PER.1
DAYS
WED
Wednesday in Period
No/Yes
PER1WED
Yes
PER.1
DAYS
THU
Thursday in Period
No/Yes
PER1THU
Yes
PER.1
DAYS
FRI
Friday in Period
No/Yes
PER1FRI
Yes
PER.1
DAYS
SAT
Saturday in Period
No/Yes
PER1SAT
Yes
PER.1
DAYS
SUN
Sunday in Period
No/Yes
PER1SUN
Yes
PER.1
DAYS
HOL
Holiday in Period
No/Yes
PER1HOL
Yes
PER.1
OCC
Occupied from
00:00
PER1_OCC
00:00
PER.1
UNC
Occupied to
00:00
PER1_UNC
24:00
Repeat for periods 2-8
HOL.L
LOCAL HOLIDAY SCHEDULES
HD.01
HOLIDAY SCHEDULE 01
HD.01
MON
Holiday Start Month
0-12
HOL_MON1
HD.01
DAY
Start Day
0-31
HOL_DAY1
HD.01
LEN
Duration (Days)
0-99
HOL_LEN1
Repeat for holidays 2-30
DAY.S
DAYLIGHT SAVINGS TIME
DS.ST
DAYLIGHT SAVINGS START
DS.ST
ST.MN
Month
1 to 12
STARTM
4
DS.ST
ST.WK
Week
1 to 5
STARTW
1
DS.ST
ST.DY
Day
1 to 7
STARTD
7
DS.ST
MIN.A
Minutes to Add
0 to 90
MINADD
60
DS.SP
DAYLIGHTS SAVINGS STOP
DS.SP
SP.MN
Month
1 to 12
STOPM
10
DS.SP
SP.WK
Week
1 to 5
STOPW
5
DS.SP
SP.DY
Day
1 to 7
STOPD
7
DS.SP
MIN.S
Minutes to Subtract
0 to 90
MINSUB
60
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...