LOCAL DISPLAY TABLES (CONT)
MODE
—
TEMPERATURES
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
AIR.T
AIR TEMPERATURES
CTRL
CONTROL TEMPS
EDT
Evaporator Discharge Tmp
-40 to 240
dF
EDT
LAT
Leaving Air Temperature
-40 to 240
dF
LAT
MAT
Mixed Air Temperature
-40 to 240
dF
MAT
R.TMP
Controlling Return Temp
-40 to 240
dF
RETURN_T
forcible
S.TMP
Controlling Space Temp
-40 to 240
dF
SPACE_T
forcible
SAT
Air Tmp Lvg Supply Fan
-40 to 240
dF
SAT
OAT
Outside Air Temperature
-40 - 240
dF
OAT
forcible
RAT
Return Air Temperature
-40 to 240
dF
RAT
forcible
SPT
Space Temperature
-40 to 240
dF
SPT
forcible
SPTO
Space Temperature Offset
-10 to 10
^F
SPTO
forcible
CCT
Air Temp Lvg Evap Coil
-40 to 240
dF
CCT
S.G.LS
Staged Heat LAT Sum
-40 to 240
dF
LAT_SGAS
S.G.L1
Staged Heat LAT 1
-40 to 240
dF
LAT1SGAS
S.G.L2
Staged Heat LAT 2
-40 to 240
dF
LAT2SGAS
S.G.L3
Staged Heat LAT 3
-40 to 240
dF
LAT3SGAS
S.G.LM
Staged Gas Limit Sw.Temp
-40 to 240
dF
LIMSWTMP
REF.T
REFRIGERANT TEMPERATURES
SCT.A
Cir A Sat.Condensing Tmp
-40 to 240
dF
SCTA
SST.A
Cir A Sat.Suction Temp.
-40 to 240
dF
SSTA
LT.A
Cir A Liquid Temperature
-40 to 240
dF
LT_A
SLT.A
Cir A Sat. Liquid Temp.
-40 to 240
dF
SLTA
SC.A
Cir A Subcooling Temp.
-100 to 200
^F
SC_A
SCT.B
Cir B Sat.Condensing Tmp
-40 to 240
dF
SCTB
SST.B
Cir B Sat.Suction Temp.
-40 to 240
dF
SSTB
LT.B
Cir B Liquid Temperature
-40 to 240
dF
LT_B
SLT.B
Cir B Sat. Liquid Temp.
-40 to 240
dF
SLTB
SC.B
Cir B Subcooling Temp.
-100 to 200
^F
SC_B
RGT.A
Suction Gas Temp Circ A
-40 to 240
dF
RGTA
DT.A1
A1 Discharge Temperature
-40 to 240
dF
DTA1
ASX1
Cir A EXV1 Suction Temp.
-40 to 240
dF
CASTEXV1
ASX2
Cir A EXV2 Suction Temp.
-40 to 240
dF
CASTEXV2
BSX1
Cir B EXV1 Suction Temp.
-40 to 240
dF
CBSTEXV1
BSX2
Cir B EXV2 Suction Temp.
-40 to 240
dF
CBSTEXV2
SH.A1
Cir A EXV1 Superheat Tmp
-100 to 200
^F
SH_A1
SH.A2
Cir A EXV2 Superheat Tmp
-100 to 200
^F
SH_A2
SH.B1
Cir B EXV1 Superheat Tmp
-100 to 200
^F
SH_B1
SH.B2
Cir B EXV2 Superheat Tmp
-100 to 200
^F
SH_B2
MODE — PRESSURES
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
AIR.P
AIR PRESSURES
SP
Static Pressure
-20 to 20
"H2O
SP
BP
Building Pressure
-20 to 20
"H2O
BP
MFDP
Main Filter Delta Press
0 to 5
"H2O
MF_DP
PFDP
Post Filter Delta Press
0 to 5
"H2O
PF_DP
REF.P
REFRIGERANT PRESSURES
DP.A
Cir A Discharge Pressure
-14 to 750
PSIG
DP_A
SP.A
Cir A Suction Pressure
-14 to 750
PSIG
SP_A
LP.A
Cir A Liquid Pressure
-14 to 750
PSIG
LP_A
DP.B
Cir B Discharge Pressure
-14 to 750
PSIG
DP_B
SP.B
Cit B Suction Pressure
-14 to 750
PSIG
SP_B
LP.B
Cit B Liquid Pressure
-14 to 750
PSIG
LP_B
MODE — SETPOINTS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
OHSP
Occupied Heat Setpoint
40 to 99
dF
OHSP
68
OCSP
Occupied Cool Setpoint
40 to 99
dF
OCSP
75
UHSP
Unoccupied Heat Setpoint
40 to 99
dF
UHSP
55
UCSP
Unoccupied Cool Setpoint
40 to 110
dF
UCSP
90
GAP
Heat-Cool Setpoint Gap
2 to 10
^F
HCSP_GAP
5
V.C.ON
VAV Occ. Cool On Delta
0 to 25
^F
VAVOCON
3.5
V.C.OF
VAV Occ. Cool Off Delta
1 to 25
^F
VAVOCOFF
2
SASP
Supply Air Setpoint
45 to 75
dF
SASP
55
SA.HI
Supply Air Setpoint Hi
45 to 75
dF
SASP_HI
55
SA.LO
Supply Air Setpoint Lo
45 to 75
dF
SASP_LO
60
SA.HT
Heating Supply Air Setpt
65 to 120
dF
SASPHEAT
85
T.PRG
Tempering Purge SASP
-20 to 80
dF
TEMPPURG
50
T.CL
Tempering in Cool SASP
5 to 75
dF
TEMPCOOL
5
T.V.OC
Tempering Vent Occ SASP
-20 to 80
dF
TEMPVOCC
65
T.V.UN
Tempering Vent Unocc. SASP
-20 to 80
dF
TEMPVUNC
50
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...